5.4 Modifiable parameters
This table lists the model choice or cycle and temperature option parameters.
F/M
ID
Description
M
P0
Appliance Type
F
P1
Appliance Model
M
P2
Boiler temperature
M
P3
Tank temperature
M
P4
Thermostop option
M
P5
Soft Start option
M
P6
Boiler temperature
offset
M
P7
Tank temperature
offset
M
P8
Real temperature
display
F
P9
Tank probe type
Note for P6 and P7: negative numbers are indicated by illumination of both decimal points (e.g.: ‐12
"1.2.")
5.5 Alarm trigger time thresholds
This table lists all the safety device trigger time thresholds.
F/
ID
Description
M
F
A0
F
A1
Boiler max. heating time
F
A2
Tank max. heating time
F
A3
Maximum water intake time
F
A4
Maximum emptying wait time
‐ CW 510/D/SD
CW 510M/MD/MSD
510M
510
2
3
2
3
80C
80C
58C
58C
0
0
1
1
0
0
4
4
1
1
1
1
Default
20 min
50 min
5 min
1 min
17
Notes
Construction version
Do not modify
Do not modify
Step 1 degree
WARNING: The actual boiler
temperature depends on
whether the connection is
single‐phase or three‐phase.
With three‐phase connection,
do not set more than 85°
Step 1 degree
0=off 1=on
0=off 1=on
Real=measured+Offset
Real=measured+Offset
0= filtered, 1= real
Do not modify
Min
Max
Notes
.
5
60
Step = 1 min
5
60
Not active with PL ON
1
20
Step = 1 min
1
2
Step = 1 min