Removal And Evacuation; Charging Procedures; Recovery - Trane A5AHC002A1B30A Installation, Operation And Maintenance Manual

Convertible air handlers 2 – 5 ton
Table of Contents

Advertisement

I I n n f f o o r r m m a a t t i i o o n n o o n n S S e e r r v v i i c c i i n n g g
be calibrated in a refrigerant-free area.) Ensure that
the detector is not a potential source of ignition and
is suitable for the refrigerant used. Leak detection
equipment shall be set at a percentage of the LFL of
the refrigerant and shall be calibrated to the
refrigerant employed, and the appropriate
percentage of gas (25 % maximum) is confirmed.
Example of leak detection fluids is b b u u b b b b l l e e m m e e t t h h o o d d .
If a leak is suspected, all naked flames shall be
removed/extinguished.
If a leakage of refrigerant is found which requires
brazing, all of the refrigerant shall be recovered from
the system, or isolated (by means of shut off valves) in
a part of the system remote from the leak.

Removal and Evacuation

When breaking into the refrigerant circuit to make
repairs - or for any other purpose - conventional
procedures shall be used. However, for flammable
refrigerants it is important that best practice be
followed, since flammability is a consideration. The
following procedure shall be adhered to:
safely remove refrigerant following local and
national regulations;
evacuate;
purge the circuit with inert gas (optional for A2L);
evacuate (optional for A2L);
continuously flush or purge with inert gas when
using flame to open circuit;
and open the circuit.
The refrigerant charge shall be recovered into the
correct recovery cylinders if venting is not allowed by
local and national codes. For appliances containing
flammable refrigerants, the system shall be purged
with oxygen-free nitrogen to render the appliance safe
for flammable refrigerants.
This process might need to be repeated several times.
Compressed air or oxygen shall not be used for
purging refrigerant systems.
For appliances containing flammable refrigerants,
refrigerants purging shall be achieved by breaking the
vacuum in the system with oxygen-free nitrogen and
continuing to fill until the working pressure is achieved,
then venting to atmosphere, and finally pulling down
to a vacuum (optional for A2L). This process shall be
repeated until no refrigerant is within the system
(optional for A2L). When the final oxygen-free nitrogen
charge is used, the system shall be vented down to
atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to
any potential ignition sources, and ventilation shall be
available.
6

Charging Procedures

In addition to conventional charging procedures, the
following requirements shall be followed.
Ensure that contamination of different refrigerants
does not occur when using charging equipment.
Hoses or lines shall be as short as possible to
minimise the amount of refrigerant contained in
them.
Cylinders shall be kept in an appropriate position
according to the instructions.
Ensure that the refrigerating system is earthed prior
to charging the system with refrigerant.
Label the system when charging is complete (if not
already).
Extreme care shall be taken not to overfill the
refrigerating system.
Prior to recharging the system, it shall be pressure-
tested with the appropriate purging gas. The system
shall be leak-tested on completion of charging but prior
to commissioning. A follow up leak test shall be carried
out prior to leaving the site.
See installation instructions below for further details.

Recovery

When removing refrigerant from a system, either for
servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure
that only appropriate refrigerant recovery cylinders are
employed. Ensure that the correct number of cylinders
for holding the total system charge is available. All
cylinders to be used are designated for the recovered
refrigerant and labelled for that refrigerant (i.e., special
cylinders for the recovery of refrigerant). Cylinders
shall be complete with pressure-relief valve and
associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs.
The recovery equipment shall be in good working
order with a set of instructions concerning the
equipment that is at hand and shall be suitable for the
recovery of the flammable refrigerant. If in doubt, the
manufacturer should be consulted. In addition, a set of
calibrated weighing scales shall be available and in
good working order. Hoses shall be complete with leak-
free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according
to local legislation in the correct recovery cylinder, and
the relevant waste transfer note arranged. Do not mix
refrigerants in recovery units and especially not in
cylinders.
If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable
level to make certain that flammable refrigerant does
not remain within the lubricant. The compressor body
18-GF81D1-1A-EN

Advertisement

Table of Contents
loading

Table of Contents