3-2. Outdoor Unit

Pressure
switch
TD sensor
Muffler
Rotary
compressor
(KTF310D46UMU)
RAV-GV1101AT8P*
(MPa)
Pd
Standard
3.45
Cooling
Overload
3.72
2.60
Low load
Standard
2.45
Heating
Overload
3.40
Low load
1.42
*
6 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
RAV-GV1401AT8P*
(MPa)
Pd
Standard
3.52
Cooling
Overload
3.78
Low load
2.60
Standard
2.65
Heating
Overload
3.40
1.47
Low load
*
6 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Packed valve
Outer dia. Ø15.88
Strainer
TS sensor
TL sensor
P
4-way valve
SHF(L)-7H-34U
Heat exchanger
Ø8, 1 row, 32 steps
FP1.3 flat fin
Ø25 × L180
Ø25 × L180
Pressure
Pipe surface temperature (°C)
(kg/cm
G)
2
Ps
Pd
Ps
(TD)
0.95
35.2
9.70
91
82
1.38
37.9
14.0
26.5
7.10
36
0.70
0.60
25.0
6.10
65
0.75
34.7
7.70
70
0.20
14.4
2.03
76
Pressure
Pipe surface temperature (°C)
(kg/cm
G)
2
Ps
Pd
Ps
(TD)
0.89
35.8
9.10
98
1.40
38.5
14.3
81
0.70
26.5
7.10
36
0.65
27.0
6.63
59
0.75
7.70
70
34.7
15.0
95
0.22
2.24
TŌ sensor
TE
sensor
(TS)
(TC)
(TE)
12
13
39
13
15
51
0.5
7
28
-1.0
34
2.7
10
53
13
-16
16
-17
(TS)
(TC)
(TE)
8
10
40
17
21
55
0.5
7
28
-0.8
42
1.2
10
13
53
19
-26
-19
- 21 -
Packed valve
Outer dia. Ø9.52
PMV
(Pulse Motor Valve)
(DPF(TS1)2.5C-01
Strainer
Strainer
Distributor
R32 : 1.9kg
*
Comp.
Fan
Hz
50
HIGH
27/19
40
HIGH
32/24
33
LOW
18/15.5
54
HIGH
20/-
48
LOW
29/27
65
HIGH
*
Comp.
Fan
Hz
75
HIGH
27/19
54
HIGH
32/24
33
LOW
18/15.5
79
HIGH
20/-
48
29/27
LOW
100.2
HIGH
Cooling
Heating
Temp
In
Out
35/-
46/-
-15/-
7/6
24/18
0/-
-15/-
Temp
In
Out
35/-
46/-
-15/-
7/6
24/18
0/-
-15/-