Toshiba RAV-GV1101AT8P-TR Service Manual page 49

Table of Contents

Advertisement

CODE No.
Data name
01
Room temperature
(Remote controller)
02
Indoor suction temperature (TA)
03
Indoor heat exchanger (Coil)
temperature (TCJ)
04
Indoor heat exchanger (Coil)
temperature (TC)
07
Indoor fan revolution frequency
F2
Indoor fan calculated operation time
F3
Filter sign time
Indoor discharge temperature*1
F8
(4-way only)
Unit
CODE No.
°C
60
61
°C
62
°C
63
65
°C
6A
6D
rpm
70
×100h
72
×1h
73
°C
F1
• The indoor discharge temperature of CODE No. [F8] is the
estimated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed
by a few seconds to ten-odd seconds.
- 49 -
Data name
Outdoor heat exchanger (Coil) temperature (TE)
Outside temperature (TO)
Compressor discharge temperature (TD)
Compressor suction temperature (TS)
Heat sink temperature (TH)
Operation current (× 1/10)
Outdoor heat exchanger (Coil) temperature (TL)
Compressor operation frequency
Outdoor fan revolution frequency (Lower)
Outdoor fan revolution frequency (Upper)
Compressor calculated operation time
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h