Toshiba RAV-GV1101AT8P-TR Service Manual page 37

Table of Contents

Advertisement

3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
Current [A]
I1
Hold
I1 – 0.5
Normal operation
4. Outdoor fan control
Model
W1
W2
GV110
230
240
GV140
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
GV110, 140 : WD tap
TL
58˚C
55˚C
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
38˚C
Rotational frequency hold
35˚C
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
Frequency down
Hold
Allocations of fan tap revolutions [rpm]
W3
W4
W5
W6
250
320
390
460
Temp.
range
38°C ≤ TO
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
0°C ≤ TO < 5°C
–4°C ≤ TO < 0°C
TO < –4°C
TO error
Model
COOL
I1 value [A]
10.0
W7
W8
W9
WA
540
650
500
600
GV110
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
GV140
Min.
Max.
W6
WD
W5
WC
W3
W7
W2
W5
W1
W3
W1
W2
OFF
W2
OFF
WD
- 37 -
GV110, 140
HEAT
10.0
WB
WC
WD
WE
700
800
880
900
Min.
Max.
Min.
W8
WD
WA
W7
WC
W9
W5
W9
W7
W4
W7
W6
W3
W5
W4
W2
W4
W3
OFF
W4
OFF
OFF
WD
OFF
WF
950
Max.
WD
WD
WB
W9
W7
W5
W4
WD