Toshiba RAV-GV1601ATP-E Installation Manual
Hide thumbs Also See for RAV-GV1601ATP-E:

Advertisement

Quick Links

AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Outdoor Unit
For commercial use
Model name:
<Heat Pump Model>
RAV-GV1601ATP-E
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-GV1601ATP-E

  • Page 1 AIR CONDITIONER (SPLIT TYPE) Installation Manual Outdoor Unit For commercial use Model name: <Heat Pump Model> RAV-GV1601ATP-E English...
  • Page 2: Table Of Contents

    8 Earthing............. 17 Single system Twin system RAV-GV1601ATP-E 1,600 1,600 9 Finishing .
  • Page 3 Thank you for purchasing this Toshiba air conditioner. Definition of Protective Gear Please read carefully through these instructions that contain important information which complies with the When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves Machinery Directive (Directive 2006/42/EC), and ensure that you understand them.
  • Page 4 – 3 – These safety cautions describe important matters concerning safety to prevent injury to users or other people and damages to property. Please read through this manual after understanding the contents below (meanings of WARNING indications), and be sure to follow the description. WARNING Indication Meaning of Indication...
  • Page 5: Precautions For Safety

    Precautions for safety • Wear protective gloves and safety work clothing during installation, servicing and removal. The manufacturer shall not assume any liability for the damage • Do not touch the aluminum fi n of the outdoor unit. You may caused by not observing the description of this manual.
  • Page 6 – 5 – • The refrigerant inside the unit is fl ammable. If the refrigerant • Outdoor units installed leaks in the room and comes in contact with fi re from a burner, (example: winter garden, garage, machinery room, etc) a heater, or a cooker, it may result in fi...
  • Page 7 • Nitrogen gas must be used for the airtight test. • When you have noticed that some kind of trouble (such as • The charge hose must be connected in such a way that it is not when an error display has appeared, there is a smell of burning, slack.
  • Page 8 – 7 – Relocation Cautions for outdoor unit installation space • In the event that the outdoor unit is installed in a small space • Only a qualifi ed installer(*1) or qualifi ed service person(*1) is and refrigerant leaks, accumulation of highly concentrated allowed to relocate the air conditioner.
  • Page 9: Accessory Parts

    Accessory parts Installation of R32 refrigerant air conditioner Part name Q’ty Shape Usage CAUTION Hand this directly to the customer. Installation Manual R32 refrigerant air conditioner installation Booklet (For other languages that do not appear in this Installation Manual, please refer to the enclosed CD-R.) •...
  • Page 10: Installation Conditions

    – 9 – Installation conditions Bender Bending pipes Conventional tools (R410A) Refrigerant recovery equipment Refrigerant recovery Conventional tools (R32 or R410A) Before installation Electrical wiring Be sure to fix the power wires and system Torque wrench Tightening flare nuts Conventional tools (R410A) Be sure to prepare to the following items before interconnection wires with clamps so that they do not installation.
  • Page 11 Installation location Necessary space for When the outdoor unit is installed in an elevated <Example> position, be sure to secure its feet. installation (Unit: mm) A location in which drain water poses any problems. WARNING Wind shield Obstacle at rear side CAUTION Install the outdoor unit properly in a location that is Wind shield...
  • Page 12 – 11 – Installation of outdoor unit Obstacle in front Obstacles in both front and rear of unit Set the out margin of the anchor bolt to 15 mm or less. Open above and to the right and left of the unit. Before installation, check the strength and Above unit is free The height of an obstacle in both the front and rear of...
  • Page 13: Refrigerant Piping

    Refrigerant piping Flaring Supplied protective bush 1. Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak. 2. Insert a flare nut into the pipe, and then flare the Refrigerant Piping Knockout of pipe cover pipe.
  • Page 14 – 13 – Tightening of connecting part Refrigerant pipe length CAUTION Align the centers of the connecting pipes Single Do not put the crescent wrench on the cap or cover. and fully tighten the flare nut with your The valve may break. fingers.
  • Page 15: Air Purging

    Air purging Pump down process Vacuum pump ■ 1. Turn off the Air Conditioner system. As shown in the figure, connect the charge hose after the manifold valve is closed completely. 2. Connect the charge hose from the manifold valve to Airtight Test ■...
  • Page 16 – 15 – How to open the valve Insulating the Pipes Gas leak inspection ■ • The temperatures at both the liquid side and gas Fully open the valves of the outdoor unit. (First fully Use a leak detector manufactured specially for side will be low during cooling so in order to prevent open the valve on the liquid side, and then fully open HFC refrigerant (R32, R410A, R134a, etc.) to...
  • Page 17: Electrical Work

    Electrical work For the air conditioner, connect a power wire with the Stripping length power cord and Indoor / following specifications. Outdoor connecting wires Remove the service panel, and you can see electric Model RAV- GV1601 1 2 3 WARNING parts on the front side.
  • Page 18: Earthing

    – 17 – Earthing Air conditioner operating conditions For proper performance, operate the air conditioner under the following temperature conditions: WARNING Cooling operation Dry bulb temp. –15 °C to 46 °C Be sure to connect the earth wire. (grounding work) Heating operation Wet bulb temp.
  • Page 19 Refrigerant recovery Steps taken to recover the refrigerant 1. Operate the indoor unit in the fan mode. When recovering the refrigerant in situations such as when relocating an indoor unit or outdoor unit, the recovery 2. Check that the LED displays are placed in their initial status. If not, place them in the initial status. operation can be performed by operating the SW01 and SW02 switches on the P.C.
  • Page 20 – 19 – Existing piping How to check the existing piping settings You can check whether the existing piping settings are enabled. The following settings are required when using a pipe Ø19.1 mm as the existing piping at the gas pipe side. 1.
  • Page 21: Troubleshooting

    Troubleshooting Appendix You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition [1] Existing piping 4. When refrigerant cannot be recovered using a to using the check codes displayed on the wired remote controller of the indoor unit. refrigerant recovery unit.
  • Page 22 – 21 – Curing of pipes When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows: Otherwise rust may be generated when moisture or Existing pipes: Cannot be used. Are there scratches or dents on the existing pipes? foreign matter due to condensation enters the pipes.
  • Page 23: Specifications

    Sound power level (dBA) Model Weight (kg) refrigerant standing mounted mounted quantity* unit unit unit RAV-GV1601ATP-E M (kg) Product information of ecodesign requirements, (Regulation (EU) 2016/2281) 2.200 41.530 4.614 3.089 http://ecodesign.toshiba-airconditioning.eu/en * Total refrigerant quantity: Refrigerant quantity pre-charged at factory. 43-EN 44-EN...
  • Page 24 – 23 – Declaration of conformity Declaration of conformity Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi,...
  • Page 25 Warnings on refrigerant leakage To Fix the Fluorinated Fill in the label as follows: ■ Greenhouse Gases Label Check of concentration limit This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
  • Page 26 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand 1124257101-1...