Beko BEKOMAT 32U F Instructions For Installation And Operation Manual page 11

Condensate drain
Table of Contents

Advertisement

Switching sequence of the valve in the alarm
mode
Trouble indication via a potential-free contact
BEKOMAT® 32U F
®
At the BEKOMAT
32U, two LEDs indicate the individ-
ual operating states.
When applying supply voltage, the BEKOMAT
carries out a self-test.
Both LEDs are lit for approximately 1 second, subse-
quently, the device changes over to the "ready-to-op-
erate" state.
Ready to operate, voltage is applied.
In the event that the condensate discharge is dis-
turbed, an alarm mode will start which is indicated by
the flashing of the red alarm LED.
Malfunction/alarm
Test of the valve function (manual drainage): press
and hold the button for approximately 2 s.
Test of the alarm function (see below): press and hold
the button for at least 1 min.
Do not use for permanent drainage.
Alarm mode:
In the event that the BEKOMAT is not empty after one
minute, a trouble indication is released:
The alarm LED flashes.
The alarm relay switches over (the signal can be
picked off potential-freely).
The valve opens every four minutes for 7.5 sec-
onds.
When the malfunction has been eliminated, the
BEKOMAT will switch back automatically into the
normal mode.
Possible trouble sources include :
Mistakes during installation
Dropping below the minimum pressure
Excessive accumulation of condensate (excess
load)
Blocked / obstructed outlet line
Extreme amount of dirt particles
Frozen pipe work
Function
®