E6-00 - Outdoor Unit: Compressor Startup Defect - Daikin Perfera ARXM25A Service Manual

Table of Contents

Advertisement

3
|
Troubleshooting
3.5.10 E6-00 – Outdoor unit: Compressor startup defect
Service manual
22
draft – 21/12/2023 13:09
Possible cause: Faulty discharge pipe thermistor or connector fault.
3 Perform a check of the outdoor unit fan motor. See Outdoor unit fan motor.
Possible cause: Faulty outdoor unit fan motor.
4 Perform a check of the compressor. See Compressor.
Possible cause: Faulty compressor or miswiring of the compressor power
supply cable.
5 Perform a check of the expansion valve. See Expansion valve.
Possible cause: Faulty expansion valve.
6 Perform a check of the 4‑way valve. See 4-way valve.
Possible cause: Faulty 4‑way valve.
7 Perform a check of the main PCB. See Main PCB.
Possible cause: Faulty main PCB.
8 Check if the refrigerant circuit is correctly charged. See
4
circuit" [
 53].
Possible cause: Refrigerant shortage.
9 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
10 Check if the refrigerant circuit is clogged. See
Possible cause: Clogged refrigerant circuit.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
Trigger
The motor rotor does
NOT rotate when the
compressor is energized.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the discharge pipe thermistor. See Thermistors.
Possible cause: Faulty discharge pipe thermistor or connector fault.
2 Check that all stop valves of the refrigerant circuit are open. See
"4.2 Refrigerant
circuit" [
Possible cause: Closed stop valve in the refrigerant circuit.
3 Check if the refrigerant circuit is clogged. See
4
"4.2 Refrigerant
circuit" [
"4.2 Refrigerant
Effect
Unit will NOT stop
operating.
Unit will stop operating
4
 53].
"4.2 Refrigerant
RXM20~50A + ARXM25~50A + FTXM20~50A + ATXM20~50A + CTXM15A
"4.2  Refrigerant
 53].
4
circuit" [
 53].
Reset
Automatic reset after a
continuous run for
10 minutes.
Manual reset via user
interface.
4
circuit" [
 53].
Split Perfera ZETA R32
ESIE23-06 – 2023.12