Mitsubishi Electric PUZ-WZ50VAA Service Manual page 64

Air to water heat pump units, outdoor unit, salt proof, r290
Hide thumbs Also See for PUZ-WZ50VAA:

Advertisement

SW2 setting
Capacity setting display
ON
1
2 3 4 5 6
Outdoor unit setting information
ON
1
2 3 4 5 6
Plate HEX liquid pipe temperature
(TH34)
ON
−40 to 90
1
2 3 4 5 6
Condensing temperature (T63HS)
−39 to 88
ON
1
2 3 4 5 6
Return water temperature
0 to 100
ON
1
2 3 4 5 6
Flow water temperature
0 to 100
ON
1
2 3 4 5 6
2-phase pipe temperature thermistor
(TH6)
-40 to 90
ON
1
2 3 4 5 6
Outdoor outside temperature (TH7)
−40 to 90
ON
1
2 3 4 5 6
OCH816
Display detail
The black square (
Explanation for display
Displayed as an outdoor capacity code.
Capacity
Code
WZ50
9
11
WZ60
WZ80
14
• The tens digit (Total display for applied setting)
Setting details
H·P / Cooling only
0 : H·P
Single phase / 3 phase
0 : Single phase 2 : 3 phase
• The ones digit
Setting details
Defrosting switch
0 : Normal
(Example) When heat pump, 3 phase and
defrosting (normal) are set up, "20" is
displayed.
−40 to 90
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
0 to 100
0 to 100
−40 to 90
(When the temperature is 0°C: or less, "–" and
temperature are displayed by turns.)
−40 to 90
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
64
) indicates a switch position.
Display details
1 : Cooling only
Display details
1 : For high humidity
Unit
Code
display
Code
display
°C
°C
°C
°C
°C
°C