Mitsubishi Electric PUZ-WZ50VAA Service Manual page 62

Air to water heat pump units, outdoor unit, salt proof, r290
Hide thumbs Also See for PUZ-WZ50VAA:

Advertisement

SW2 setting
Pipe temperature/Liquid (TH3)
−40 to 90
ON
1
2 3 4 5 6
Discharge temperature (TH4)
-20 to 217
ON
1
2 3 4 5 6
Output step of outdoor FAN
ON
0 to 16
1
2 3 4 5 6
The number of ON/OFF times of com-
pressor
ON
0 to 9999
1
2 3 4 5 6
Compressor integrating operation times
0 to 9999
ON
1
2 3 4 5 6
Compressor operating current
ON
0 to 50
1
2 3 4 5 6
Compressor operating frequency
0 to 225
ON
1
2 3 4 5 6
Primary LEV opening pulse
0 to 500
ON
Heating: LEV-B
Cooling: LEV-A
1
2 3 4 5 6
Error postponement code history (1)
ON
of outdoor unit
1
2 3 4 5 6
Operation mode on error occurring
ON
1
2 3 4 5 6
OCH816
Display detail
The black square (
Explanation for display
−40 to 90
(When the coil thermistor detects 0°C or below, "–"
and temperature are displayed by turns.)
(Example) When −10°C;
0.5 s
-20 to 217
(When the discharge thermistor detects 100°C or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105°C;
0.5 s
0 to 16
0 to 9999
(When the number of times is 100 or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 42500 times (425 ×100 times);
0.5 s
0 to 9999
(When it is 100 hours or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 2450 hours (245 ×10 hours);
0.5 s
0 to 50
Note: Value after the decimal point will be truncated.
0 to 255
(When it is 100 Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125 Hz;
0.5 s
0 to 500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 s
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Operation mode of when operation stops due to
error is displayed by setting SW2 like below.
(SW2)
ON
1
2 3 4 5 6
62
) indicates a switch position.
0.5 s
2 s
10
0.5 s
2 s
1
05
100 times
0.5 s
2 s
4
25
0.5 s
2 s
2
45
0.5 s
2 s
1
25
0.5 s
2 s
1
50
Unit
°C
°C
Step
10 hours
A
Hz
Pulse
Code
display
Code
display