Specifications
Class A/B, NAC power
Class D door holder power
Special application Class A/B aux power
UZC
2.8 ohm max line impedance
NAC 3 and NAC 4- TB3
Power-limited (Class 2), 24VDC, 1.5 Amps
Special applications, 150ma regulated,
Class A/B, NAC power
Class D door holder power
Special application Class A/B aux power
UZC
2.8 ohm max line impedance
Battery Connection- TB9
Charges 7-100 AH batteries
Charging current: 1A, 2A, and 4.25A
Charging voltage: 27.6VDC nominal
Remote Sync Input- TB6
Power-limited (Class 2)
Aux Power 1/Aux Power2- TB7
24VDC, 1.5Amps Class A/B, power-limited (Class 2), special applications, resettable/Non-Resettable
AC Power Connection- TB8
2.5A, 120VAC, 50/60 HZ, non-power-limited
1.25A, 240VAC, 50/60 Hz, non-power-limited
1.2.3 SLM-318 Signaling Loop Module
SLC Connection- TB1
24VDC, Class A/B/X, power-limited, 50 ohms max.
Alarm current: 210mA
Standby current: 159mA
1.2.4 Accessories/Sub-assemblies/Networked Panels Maximum System Capacity:
Monitor and Control Modules- 159 per loop, up to 1,590 total in FlashScan; 99 per loop, up to 990 in CLIP mode
Detectors- 159 per loop, up to 1,590 total in FlashScan; 99 per loop, up to 990 in CLIP mode
Signaling Line Circuits (SLC) 10
N16 Fire Alarm Control Panel System Size- High-Speed Noti•Fire•Net - 200 Nodes, Noti•Fire•Net - 103 Nodes. 54 nodes when DVC
is used in network paging.