Amplifier Fault Inputs; Forced-Air Cooling; Figure 2-2: Ac Output Connections - Aerotech UFM-ST Hardware Manual

Noise filter module
Hide thumbs Also See for UFM-ST:
Table of Contents

Advertisement

UFM-ST

2.1.2. Amplifier Fault Inputs

The UFM-ST three-terminal output connector is the filter AC output (load) connector. Terminals AC1
and AC2 are the AC power connections and are wired to the equipment being filtered. The Ground
terminal (connected internally to the Input ground and the external Ground Stud) and is typically
connected to the ground of the equipment being supplied by this filter.
Wiring to the UFM-ST filter must use #16 AWG wires or larger and have an insulation rating of at
least 300 V.
Figure 2-2:
AC Output Connections

2.2. Forced-Air Cooling

The UFM-ST filter requires additional cooling for operation above 8 A
into the ventilation holes on the UFM-ST filter case. Sufficient cooling is being provided if the UFM-ST
case temperature is less than 45°C during all operation conditions.
20
Hardware Manual
. Air flow must be directed
rms
www.aerotech.com