Mitsubishi Electric FR-A802-F Series Instruction Manual page 145

Table of Contents

Advertisement

 Fuse selection
Fuses are selected based on IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274.
For installation in the United States, the following semi-conductor fuses must be provided, in accordance with the
National Electrical Code and any applicable local codes. For installation in Canada, the following semi-conductor
fuses must be provided, in accordance with the Canada Electrical Code and any applicable provincial codes. Always
install the following semiconductor fuses for branch circuit protection.
• 6-phase rectification
Converter model
FR-CC2-H315K
FR-CC2-H355K
FR-CC2-H400K
FR-CC2-H450K
FR-CC2-H500K
FR-CC2-H560K
FR-CC2-H630K
• 12-phase rectification
Converter model
FR-CC2-H315K
FR-CC2-H355K
FR-CC2-H400K
FR-CC2-H450K
FR-CC2-H500K
FR-CC2-H560K
FR-CC2-H630K
 Capacitor discharge time / Temps de décharge du condensateur
CAUTION -Risk of Electric Shock-
Before wiring or inspection, check that the LED indicator turns OFF. Any person who is involved in wiring or inspection
shall wait for 10 minutes or longer after power OFF and check that there are no residual voltage using a digital
multimeter or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous.
ATTENTION -Risque de choc électrique-
Avant le câblage ou l'inspection, vérifier que le témoin LED s'éteint. Toute personne impliquée dans le câblage ou
l'inspection doit attendre 10 minutes ou plus après la mise hors tension et vérifier l'absence de tension résiduelle à
l'aide d'un multimètre numérique ou similaire. Le condensateur est chargé avec une haute tension pendant un certain
temps après la mise hors tension, ce qui est dangereux. Précautions pour ouvrir le dispositif de protection du circuit
de dérivation.
 Wiring to the power supply and the motor
• Refer to the National Electrical Code (Article 310) regarding the allowable current of the cable. Select the cable
size for 125% of the rated current according to the National Electrical Code (Article 430). For wiring the input (R/
L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL listed copper, stranded wires (rated at
75°C) and round crimp terminals. Crimp the terminals with the crimping tool recommended by the terminal
manufacturer.
 Short circuit ratings
• Suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 500 V
Maximum.
Cat. No.
PC33UD69V1250TF
PC33UD69V1250TF
PC33UD69V1400TF
PC33UD69V1400TF
PC33UD69V1400TF
PC33UD69V1400TF
PC33UD69V1400TF
Cat. No.
PC33UD69V900TF
PC33UD69V900TF
PC33UD69V1100TF
PC33UD69V1100TF
PC33UD69V1100TF
PC33UD69V1100TF
PC33UD69V1100TF
2
Manufacturer
Mersen
Mersen
Mersen
Mersen
Mersen
Mersen
Mersen
Manufacturer
Mersen
Mersen
Mersen
Mersen
Mersen
Mersen
Mersen
Rating (A)
1250
1250
1400
1400
1400
1400
1400
Rating (A)
900
900
1100
1100
1100
1100
1100
BCN-C22005-1010