Figure 2-3 - Line Reactor Sizing Recommendations - Gardner Denver VS200-250B Operating And Service Manual

Variable speed single stage stationary base-mounted compressor
Table of Contents

Advertisement

Electrical Wire Routing – Routing of the electrical power wires into the electrical hardware enclosure is
best done through its roof area.
Line Reactor – A line reactor provides conditioning of the electrical power supply to the compressor
package by attenuating noise and fluctuations. It shall be required in your particular application if any of
the following conditions exist:
Transformer KVA is greater than recommended – see Figure 2-3, page 16.
Line has switched Power Factor correction capacitors.
Existing line reactor not properly sized – see Figure 2-3, page 16.
Other large loads on the same power feed as the compressor.
GD Model
Volts
VS200
400/480
VS250
400/480
Figure 2-3 – LINE REACTOR SIZING RECOMMENDATIONS
GROUNDING – Equipment must be properly grounded in accordance with the National Electrical Code
and/or applicable local codes.
Failure to properly ground the compressor package could result in injury or
death. Install ground wiring in accordance with the National Electrical Code
and any applicable local codes.
MOTOR LUBRICATION - Long time satisfactory operation of an electric motor depends in large
measure on proper lubrication of the bearings. Refer to Section 13 of this manual for complete motor
lubrication specifications and details.
VFD HP RATINGS
300
350
13-18-614
Page 16
3% Line Reactor
Max KVA
GD Part Number
3000
90500145
3500
90500146