Electrical Wire Routing – Routing of the electrical power wires into the electrical hardware enclosure is
best done through its roof area.
Line Reactor – A line reactor provides conditioning of the electrical power supply to the compressor
package by attenuating noise and fluctuations. It shall be required in your particular application if any of
the following conditions exist:
Transformer KVA is greater than recommended – see Figure 2-3, page 18.
Line has switched Power Factor correction capacitors.
Existing line reactor not properly sized – see Figure 2-3, page 18.
Other large loads on the same power feed as the compressor.
GD Model
Volts
VS80
400/480
VS80
575
VS110
400/480
VS110
575
Figure 2- 3 – LINE REACTOR SIZING RECOMMENDATIONS
GROUNDING – Equipment must be properly grounded in accordance with the National Electrical Code
and/or applicable local codes.
Failure to properly ground the compressor package could result in injury or death.
Install ground wiring in accordance with the National Electrical Code and any
applicable local codes.
MOTOR LUBRICATION - Long time satisfactory operation of an electric motor depends in large measure
on proper lubrication of the bearings. Refer to Section 13, page 75 of this manual for complete motor
lubrication specifications and details.
VFD HP RATINGS
107
107
147
147
`
13-18-612
Page 18
3% Line Reactor
Max KVA
GD Part Number
1000
90500142
1000
90500141
1500
90500144
1000
90500142