NORDfire FDMQ Fire Damper Square dampers from 150×150 mm to 1500×800 mm CE certified acc. to EN 15650 Fire resistance up to EIS 90 External casing leakage class C, Internal leakage class 2 acc. to EN 1751 Manual or electrical...
® NORDfire | FDMQ 1. General 1.1 Description Fire dampers are shutters in ducts of air-conditioning devices that prevent the spread of fire and combustion products from one fire segment to the other one by means of closing the duct in the points of fire separating constructions.
® NORDfire | FDMQ 1.3 Working conditions Exact damper function is provided under the following conditions: • maximum air circulation speed: 12 m/s • maximum pressure difference: 1200 Pa • the air circulation in the whole damper section must be secured steady over the entire surface. Dampers can be installed in arbitrary position.
Page 5
® NORDfire | FDMQ Design .80 Design .01 with manual control can be complemented with two limit switches signaling of the damper blade position “CLOSED” and “OPEN”. Cables are connected directly to limit switches. Fig. 5. Design .80 Limit switch Limit switch “OPEN”...
Page 6
® NORDfire | FDMQ 2.2 Design with spring return actuator Design .40 and .50 The fire dampers are equipped with Belimo spring return actuators with thermoelectric activation device BAT. The spring return actuator types are BFL, BFN or BF depending on the damper size. (Further mentioned as „actuator“).
Page 10
® NORDfire | FDMQ Thermoelectric activation device BAT If the thermal fuse Tf1 is interrupted (due to temperature outside the duct), it is necessary to replace the spring return actuator. Thermoelectric activation device BAT is integral part of the actuator. If the thermal fuse Tf2 is interrupted (due to temperature inside the duct), only the spare part ZBAT 72 (95/120/140) needs to be replaced (acc.to the activation temperature).
® NORDfire | FDMQ 3. Material, dimensions, weights and effective area 3.1 Material Damper casings are made from galvanized sheet metal without further surface treatment. Damper blades are made from fire resistant asbestos free boards made of mineral fibres. Manual control have cover made of mechanically resistant and durable plastic and the other parts are galvanized without further surface treatment.
Page 12
® NORDfire | FDMQ 3.2 Dimensions Fig. 7. FDMQ with manual control A - 10 A - 10 1 – Damper casing 2 – Manual control 3 – Damper blade 4 – Inspection opening cover 5 – Sensor sticker 6 – Hole for camera Fig.
Page 13
® NORDfire | FDMQ 3.3 Damper blade overlaps Open damper blade overlaps the damper casing by the value “a” or “c”. These values are specified in Tab. 5. Values “a” and “c” has to be respected when projecting following air-conditioning duct. Fig.
Page 14
® NORDfire | FDMQ Tab. 5. Technical parameters Weight Weight Effect. Spring Effect. Spring A×B Manual A×B Manual area return area return man. actu. man. actu. (mm) contr. (mm) contr. Sef (m actu. Sef (m actu. (kg) (kg) (kg) (kg) ×630 0,0989 150×150...
Page 15
® NORDfire | FDMQ Weight Weight Effect. Spring Effect. Spring A×B Manual A×B Manual area return area return man. actu. man. actu. (mm) contr. (mm) contr. Sef (m actu. Sef (m actu. (kg) (kg) (kg) (kg) ×250 14,5 0,0472 ×650 19 234 23,5 26,5 0,1712...
Page 16
® NORDfire | FDMQ Weight Weight Effect. Spring Effect. Spring A×B Manual A×B Manual area return area return man. actu. man. actu. (mm) contr. (mm) contr. Sef (m actu. Sef (m actu. (kg) (kg) (kg) (kg) ×315 0,1063 ×750 69 284 35,5 38,5 0,3596...
Page 17
® NORDfire | FDMQ Weight Weight Effect. Spring Effect. Spring A×B Manual A×B Manual area return area return man. actu. man. actu. (mm) contr. (mm) contr. Sef (m actu. Sef (m actu. (kg) (kg) (kg) (kg) ×450 27,5 30,5 0,2329 ×180 21,5 0,0788...
Page 18
® NORDfire | FDMQ Weight Weight Effect. Spring Effect. Spring A×B Manual A×B Manual area return area return man. actu. man. actu. (mm) contr. (mm) contr. Sef (m actu. Sef (m actu. (kg) (kg) (kg) (kg) ×560 0,3836 ×280 35,5 0,2311 ×600 0,4146...
Page 20
® NORDfire | FDMQ Minimum distance between the fire dampers and the construction • minimum distance 200 mm between dampers, according to EN 1366-2 • minimum distance 75 mm between damper and construction (wall/ceiling), according to EN 1366-2 • recommended minimum distance 150 mm necessary for access to the actuator •...
Page 21
® NORDfire | FDMQ Fig. 12. Dimensions of an installation opening Mortar or gypsum • min. A(B)+100 • max. A(B)+300 Stuffing box with fire protective boards • min. A(B)+80 • max. A(B)+220 Weichschott • min. A(B)+80 • max. A(B)+800 Examples of constructions for fire damper installation The fire damper can be installed into: •...
Page 22
® NORDfire | FDMQ Wall/Ceiling Fire Placement Method of installation Page min. thickness resist. (mm) Mortar or gypsum 2 dampers in battery - mortar or gypsum 4 dampers in battery - mortar or gypsum In gypsum wall Weichschott system EI 90 (v i↔o) S construction Mineral wool with fire-resistant...
Page 23
® NORDfire | FDMQ 4.3 In solid wall construction Fig. 13. In solid wall construction - mortar or gypsum For connection of following duct, see page 79. EIS 90 EIS 90 ≥ 100 1 – FDMQ 2 – Solid wall construction 3 –...
Page 24
® NORDfire | FDMQ Fig. 14. In solid wall construction - 2 dampers in battery - mortar or gypsum EIS 90 ≥ 100 A(B)-1 A(B)-6 1 – FDMQ 2 – Solid wall construction 3 – Mortar or gypsum 4 – Profile with threaded rod see pages 75 to 78 5 –...
Page 25
® NORDfire | FDMQ Fig. 15. In solid wall construction - 4 dampers in battery - mortar or gypsum EIS 90 ≥ 100 A(B)+29 A(B)-1 A(B)-6 A(B)+24 1 – FDMQ 2 – Solid wall construction 3 – Mortar or gypsum 4 –...
Page 26
® NORDfire | FDMQ Fig. 16. In solid wall construction – Weichschott system EIS 90 For connection of following duct, see page 79. ≥ 100 * HILTI system can be replaced by a similar system with 1 – FDMQ the same or higher thickness, density, fire reaction class, 2 –...
Page 27
® NORDfire | FDMQ Fig. 17. In solid wall construction - mineral wool with fire-resistant coating and fire-resistance boards EIS 90 For connection of following duct, see page 79. ≥ 100 ≤ 300 1 – FDMQ 2 – Solid wall construction 3 –...
Page 28
® NORDfire | FDMQ Fig. 18. In solid wall construction - installation next to the wall/ceiling - mortar or gypsum + mineral wool EIS 90 ≥ 100 ≥ 150 ⑤ 1 – FDMQ For connection of following duct, see page 79. 2 –...
Page 29
® NORDfire | FDMQ 4.4 Installation outside solid wall constrution Fig. 19. Outside solid wall constrution - ISOVER Ultimate Protect - mortar or gypsum EIS 60 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ISOVER manufacturer's instructions.
Page 30
® NORDfire | FDMQ Fig. 20. Outside solid wall constrution - ISOVER Ultimate Protect - Weichschott system EIS 60 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ISOVER manufacturer's instructions. The damper and the duct must be suspended separately.
Page 31
® NORDfire | FDMQ Fig. 21. Outside solid wall constrution - mineral wool ROCKWOOL - mineral wool with fire-resistant coating and fireresistant board EIS 90 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ROCKWOOL manufacturer's instructions.
Page 32
® NORDfire | FDMQ 4.5 In gypsum wall construction Fig. 22. In gypsum wall construction - mortar or gypsum EIS 90 For connection of following duct, see page 79. ≥ 100 1 – FDMQ 2 – Gypsum wall construction 3 – Mortar or gypsum 4 –...
Page 33
® NORDfire | FDMQ Fig. 23. In gypsum wall construction - 2 dampers in battery - mortar or gypsum EIS 90 ≥ 100 A(B)-1 A(B)-6 1 – FDMQ 2 – Gypsum wall construction 3 – Mortar or gypsum 4 – Profile with threaded rod, see pages 75 to 78 5 –...
Page 34
® NORDfire | FDMQ Fig. 24. In gypsum wall construction - 4 dampers in battery - mortar or gypsum EIS 90 ≥ 100 A(B)+29 A(B)-1 A(B)-6 A(B)+24 1 – FDMQ 2 – Gypsum wall construction 3 – Mortar or gypsum 4 –...
Page 35
® NORDfire | FDMQ Fig. 25. In gypsum wall construction - Weichschott system EIS 90 For connection of following duct, see page 79. ≥ 100 * HILTI system can be replaced by a similar system with 1 – FDMQ the same or higher thickness, density, fire reaction class, 2 –...
Page 36
® NORDfire | FDMQ Fig. 26. In gypsum wall construction - mineral wool with fire-resistant coating and fire-resistance boards EIS 90 For connection of following duct, see page 79. ≥ 100 ≤ 300 1 – FDMQ 2 – Gypsum wall construction 3 –...
Page 37
® NORDfire | FDMQ Fig. 27. In gypsum wall construction - installation next to the wall/ceiling - mortar or gypsum + mineral wool EIS 90 ≥ 100 ≥ 150 ⑤ 1 – FDMQ 2 – Gypsum wall construction For connection of following duct, see page 79. 3 –...
Page 38
® NORDfire | FDMQ 4.6 Installation outside gypsum wall constrution Fig. 28. Outside gypsum wall constrution - ISOVER Ultimate Protect - mortar or gypsum EIS 60 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ISOVER manufacturer's instructions.
Page 39
® NORDfire | FDMQ Fig. 29. Outside gypsum wall constrution - ISOVER Ultimate Protect - Weichschott system EIS 60 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ISOVER manufacturer's instructions. The damper and the duct must be suspended separately.
Page 40
® NORDfire | FDMQ Fig. 30. Outside gypsum wall constrution - mineral wool ROCKWOOL - mineral wool with fire-resistant coating and fireresistant board EIS 90 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ROCKWOOL manufacturer's instructions.
Page 41
® NORDfire | FDMQ 4.7 Installation in sandwich wall construction Fig. 31. In sandwich wall construction - Weichschott system with fire-resistant boards EIS 90 For connection of following duct, see page 79. ≥ 100 ≤ 300 * HILTI system can be replaced by a similar system with the same or higher thickness, density, fire reaction class, tested according to EN 1366-3.
Page 42
® NORDfire | FDMQ 4.8 Shaft walls Rigips Shaft wall is a vertical, non-bearing partition construction meeting the double-sided fire requirements. The shaft wall can be mounted only from one side. No mineral insulation is used in the construction. First of all, the shaft wall construction must be laid out. Apart from other vertical constructions, the perimeter sections must be fitted with connection sealing made from A1 or A2 fire reaction materials (for instance floor strips Orsil N/PP).
Page 43
® NORDfire | FDMQ Fig. 32. In shaft wall Rigips - mortar or gypsum EIS 90 For connection of following duct, see page 79. Follow shaft wall manufacturer's instructions. ≥ 100 ≤ 250 1 – FDMQ 2 – Mortar or gypsum 3 –...
Page 44
® NORDfire | FDMQ Fig. 33. In shaft wall Rigips - installation frame E1 EIS 90 For connection of following duct, see page 79. Follow shaft wall manufacturer's instructions. Installation frame can be installed on the damper or delivered separately. For more E1 frame details, see page 57.
Page 45
® NORDfire | FDMQ 4.9 In solid ceiling construction Fig. 34. In solid ceiling construction - mortar or gypsum EIS 90 For connection of following duct, see page 79. 1 – FDMQ 2 – Solid ceiling construction 3 – Mortar or gypsum * min.
Page 46
® NORDfire | FDMQ Fig. 35. In solid ceiling construction - 2 dampers in one opening - mortar or gypsum EIS 90 * min. 110 mm - Concrete min. 125 mm - Aerated concrete A(B)-1 A(B)-6 1 – FDMQ 2 – Solid ceiling construction 3 –...
Page 47
® NORDfire | FDMQ Fig. 36. In solid ceiling construction - 4 dampers in one opening - mortar or gypsum EIS 90 ≥ 110 * A(B)-1 A(B)+29 A(B)-6 A(B)+24 * min. 110 mm - Concrete min. 125 mm - Aerated concrete 1 –...
Page 48
® NORDfire | FDMQ Fig. 37. In solid ceiling construction - Weichschott system EIS 90 For connection of following duct, see page 79. ** min. 110 mm - Concrete min. 125 mm - Aerated concrete ≥ 20 * HILTI system can be replaced by a similar system with 1 –...
Page 49
® NORDfire | FDMQ Fig. 38. In solid ceiling construction - mineral wool with fire-resistant coating and fire-resistance boards EIS 90 For connection of following duct, see page 79. * min. 110 mm - Concrete min. 125 mm - Aerated concrete ≥...
Page 50
® NORDfire | FDMQ 4.10 Outside solid ceiling construction Fig. 39. Outside solid wall constrution - mineral wool ROCKWOOL - mineral wool with fire-resistant coating and fireresistant board EIS 90 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. When installing the insulation, follow the ROCKWOOL manufacturer's instructions.
Page 51
® NORDfire | FDMQ Fig. 40. Outside solid ceiling construction - concreting EIS 90 For connection of following duct, see page 79. The duct must be suspended or supported on both sides of the damper acc. to national rules. Load of the suspension system depends on weight of the fire damper and duct system, see page 73.
[m.s ] air flow speed in nominal damper section [kg.m ] air density ® NORDfire | FDMQ coefficient of local pressure loss for the nominal damper section (see Tab. 11.1.1.) Determination of pressure loss by using diagram = 1,2 kg.m 5.
® NORDfire | FDMQ 7. Product marking FDMQ A×B Type Nominal size Design Manual control and thermal Manual control and thermal (Zone 1,2) Manual control and thermal with a terminal switch („CLOSED“) Manual control and thermal with a terminal switch („CLOSED“) (Zone 1,2) With actuator BF 230-TN (BFL, BFN 230-T) - voltage AC 230 V With actuator BF 24-TN (BFL, BFN 24-T) - voltage AC/DC 24 V Manual control and thermal with two terminal switches („OPEN“, „CLOSED“)
® NORDfire | FDMQ 8. Installation frames Tab. 10. List of installation frames and installation options Wall thickness (mm) Solid wall construction Gypsum wall construction Solid ceiling construction Inst. Outside Outside Outside frame construc- construc- construc- construc- construc- construc- costruc- construc- construc- tion...
Page 57
® NORDfire | FDMQ 8.1 Installation frame E1 Installation frame E1 is designed for installation without additional sealing of the penetration into: • Solid wall construction • Gypsum wall construction • Solid ceiling construction Installation frame is equipped with an intumescent sealing on the inside and outside. This sealing fills the gap between the damper casing and frame and between the frame and construction in the event of a fire.
Page 58
® NORDfire | FDMQ Fig. 41. In solid wall construction - installation frame E1 For connection of following duct, see page 79. Installation frame can be installed on the damper or delivered separately. EIS 90 1 – FDMQ ≥ 100 2 –...
Page 59
® NORDfire | FDMQ Fig. 42. Gypsum wall construction - installation frame E1 For connection of following duct, see page 79. Installation frame can be installed on the damper or delivered separately. EIS 90 Detail of the wall > 100 mm >...
Page 60
® NORDfire | FDMQ Fig. 43. Solid ceiling construction - installation frame E1 For connection of following duct, see page 79. Installation frame can be installed on the damper or delivered separately. EIS 90 * min. 110 mm - Concrete min.
Page 61
® NORDfire | FDMQ 8.2 Installation frame E2 Installation frame E2 is designed for installation with steel insert and mortar or gypsum into: • Solid wall construction • Solid ceiling construction The damper is equipped with an intumescent sealing on the casing. This sealing fills the gap between the steel insert and the damper in the event of a fire.
Page 62
® NORDfire | FDMQ Fig. 44. In solid wall construction - installation frame E2 For connection of following duct, see page 79. EIS 90 Installation frame can be installed on the damper or delivered separately. ≥ 100 1 – FDMQ 2 –...
Page 63
® NORDfire | FDMQ Fig. 45. In solid ceiling construction - installation frame E2 For connection of following duct, see page 79. EIS 90 Installation frame can be installed on the damper or delivered separately. 1 – FDMQ 2 – Installation frame 3 –...
Page 64
® NORDfire | FDMQ 8.3 Installation frame E3 Installation frame E is designed for installation into: • Gypsum wall construction The damper is equipped with an intumescent sealing on the casing. This sealing fills the gap between the damper casing and frame in the event of a fire. The frame is equipped with an intumescent sealing on external side. This sealing fills the gap between the frame and construction in the event of a fire.
Page 65
® NORDfire | FDMQ Fig. 46. In gypsum wall construction - installation frame E3 EIS 90 For connection of following duct, see page 79. Installation frame can be installed on the damper or delivered separately. Detail of the wall > 100 mm >...
Page 66
® NORDfire | FDMQ 8.4 Installation frame E4 Installation frame E4 is designed for installation on: • Solid wall construction • Solid ceiling construction • Outside solid ceiling construction with concreting Installation frame is equipped with an intumescent sealing on the inside. This sealing fills the gap between the damper casing and frame in the event of a fire.
Page 67
® NORDfire | FDMQ Fig. 47. In solid wall construction - installation frame E4 For connection of following duct, see page 79. EIS 90 Installation frame can be installed on the damper or delivered separately. ≥ 100 1 – FDMQ 2 –...
Page 68
® NORDfire | FDMQ Fig. 48. In solid ceiling construction - installation frame E4 For connection of following duct, see page 79. EIS 90 Installation frame can be installed on the damper or delivered separately. * min. 110 mm - Concrete min.
Page 69
® NORDfire | FDMQ Fig. 49. Outside solid ceiling construction - concreting - installation frame E4 EIS 90 For connection of following duct, see page 79. The duct must be suspended or supported on both sides of the damper acc. to national rules. Load of the suspension system depends on weight of the fire damper and duct system, see page 73.
Page 70
® NORDfire | FDMQ 8.5 Installation frame E5 Installation frame E5 is designed for installation without additional sealing of the penetration for: • Installation in gypsum walls under flexible ceilings with a maximum movement of 40 mm • Wall thicknesses 100 to 150 mm Installation frame is equipped with an intumescent sealing on the inside and outside.
Page 71
® NORDfire | FDMQ Fig. 50. In solid ceiling construction – installation frame E5 Installation directly on the ceiling For connection of following duct, see page 79. EIS 90 Installation frame can be installed on the damper or delivered separately. Gypsum construction must be made in accordance with the specifications of the wall system manufacturer.
Page 72
® NORDfire | FDMQ 8.6 Installation frame E6 Installation frame E6 is designed for installation without additional sealing of the penetration into: • Installation outside solid wall/ceiling construction with insulation from fire-resistant boards Installation frame is equipped with an intumescent sealing on the inside. This sealing fills the gap between the damper casing and frame in the event of a fire.
Page 73
® NORDfire | FDMQ Fig. 52. Outside solid wall construction - insulation from fire-resistant boards - mortar or gypsum - installation frame E6 EIS 90 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. Insulation must be suspended using threaded rods and mounting profiles or other mounting system, according to national standards.
Page 74
® NORDfire | FDMQ Fig. 53. Outside solid ceiling construction - insulation from fire-resistant boards - mortar or gypsum - installation frame E6 For connection of following duct, see page 79. Minimum and maximum distance between the wall and fire damper is unlimited. Insulation must be suspended using threaded rods and mounting profiles or other mounting system, according to national standards.
® NORDfire | FDMQ 9. Suspension Systems Mounting to the ceiling wall The dampers must be suspended using threaded rods and mounting profiles. Their dimensioning depend on the weight of the damper. The dampers and the duct must be suspended separately. Following air-conditioning duct must be suspended or supported so that all load transfer from the following duct to the damper flanges is absolutely excluded.
Page 76
® NORDfire | FDMQ Fig. 54. Example of placing of mounting profiles HILTI max. 50 1 – FDMQ 2 – Threaded rod M8 - M12 3 – Support HILTI MQ-41 or MQ-41/3 4 – Bored plate HILTI MQZ-L 5 – Washer for M8 - M12 6 –...
Page 77
® NORDfire | FDMQ Fig. 55. Example of fixing FDMQ to the wall ceiling In solid wall construction In gypsum wall construction 1 – Solid wall construction 2 – Gypsum wall construction 3 – FDMQ 4 – Duct 5 – Penetration 6 –...
Page 78
® NORDfire | FDMQ Fig. 56. Example of fixing FDMQ to the ceiling In solid ceiling construction 1 – Solid ceiling construction 2 – FDMQ 3 – Duct 4 – Penetration 5 – Profile with threaded rod, see page 75 6 –...
Page 79
® NORDfire | FDMQ 9.1 Example of duct connection Electrically conductive connection Electrically conductive connection * at least one connection must be electrically conductive * at least one connection must be electrically conductive 1 – FDMQ 2 – Duct 3 – Extension piece (if required) 4 –...
® NORDfire | FDMQ 10. Transportation, storage and warranty 10.1 Logistic terms Dampers are delivered on pallets. As standard, the dampers are wrapped in plastic foil for protection during transport and must not be used for long-term storage. Temperature changes during transport can cause conden- sation of water inside the packaging and thereby cause corrosion of materials used in the dampers (e.g.
Page 81
® NORDfire | FDMQ Limit switches If the damper is equipped with limit switches and these switches are not used during operation (e.g. because of a project change), they can be left on the damper and not connected (they need not be dismounted). On the other hand, if the limit switch is to be added to the damper design, the change can be implemented by change kit.
Page 82
® NORDfire | FDMQ Fig. 57. Change of manual control for the actuator or vice versa 1 – Damper 2 – Mouting plate 3 – Sealing cover 4 – Sealing of a mouting plate 5 – Cover of a mouting plate 6 –...
Page 83
® NORDfire | FDMQ Reinforcement frame VRM-Q If the damper is installed outside the fire separation construction, a damper side A ≥ 800 mm and fire resistance is EIS 90, VRM-Q reinforcement frame must be used. For lower fire resistance than EIS 90, VRM-Q reinforcement frame is not necessary! VRM-Q is mounted only on "A"...
Page 84
® NORDfire | FDMQ Protective cladding boards Protective cladding boards must be used as a part of installation with weichschott system. Can be ordered from MANDIK (installed on the damper or as an accessory) or can be sourced from local supplier. If protective cladding boards are required, this must be specified in the ordering key.
® NORDfire | FDMQ 12. Entry into service and revisions Before putting the damper into operation, serviceability checks and functional tests must be carried out including testing of functionality of all electrical elements. After putting into operation these serviceability checks must be carried at least twice a year.
Page 86
® NORDfire | FDMQ For dampers with actuators, following checks must be carried out Check the rotation of the blade to "CLOSED" failure position after disconnection the power supply of the actua- tor (e.g. by pressing the test button on the thermoelectric activation device BAT or by disconnection the power supply from electrical fire signalization).
Page 87
ETS NORD AS Address: Peterburi tee 53 11415 Tallinn Estonia Phone: +372 680 7360 info@etsnord.ee www.etsnord.ee ETS NORD Finland Address: Pakkasraitti 4 04360 Tuusula Finland Phone: +358 40 184 2842 info@etsnord.fi www.etsnord.fi ETS NORD Sweden Address: Järsjögatan 7 692 35 Kumla...