Full Gauge Controls TC-900E Log Quick Start Manual

Digital controller for freezing systems with defrost scheduling and internal datalogger

Advertisement

Quick Links

Have this manual in the palm of
your hand by FG Finder application.
1. DESCRIPTION
Designed to better safeguard frozen products.
Defrost & Fan), 2 temperature sensors, 2 digital inputs, real-time clock, data logger and light intensity
sensor. A third temperature sensor can be connected to one of it's digital input for either defrost
management of second evaporator; condenser temperature control or to activate economic set point.
Other salient features include hour-meter to clock the working hours of compressor for preventive
maintenance, internal buzzer, IP65 frontal, min-max temperature record, temperature sensor response
time control, fast freezing mode, tamper-proof function, control functions shutdown and RS485 serial
communication port for Sitrad real-time monitoring and management.
e
TC-900
Log
The
allows you to configure the RS-485 communication port for the MODBUS-RTU
protocol. For more information about the implemented commands and the registration table, contact
Full Gauge Controls.
Product conforming to UL Inc. (United States and Canada) and NSF (United States).
2. APPLICATION
• Walk-in freezers
• Display freezers
• Upright freezers
3. TECHNICAL SPECIFICATIONS
Power supply
Control temperature
Operating temperature
Load current (outputs)
Maximum consumption of device
Operating humidity
Dimensions (mm)
Dimensions of the clipping for fixing
of the instrument
4. INDICATIONS AND KEYS
Defrost indication LED
Fan indication LED
Compressor output
indication LED
Quick Access
Menu Key
Set key
e
TC-900
5. INSTALLATION - ASSEMBLING AND ELECTRICAL
CONNECTIONS
ATTENTION
FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO AVOID LIQUID CONTACT, THE CUT FOR THE CONTROLLER MUST BE OF
70,5X29mm MAXIMUM. THE SIDE LOCKS MUST BE FIXED SO IT PRESSES THE RUBBER SEALING AVOIDING
INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.
IMPORTANT
THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:
SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER TERMINALS;
Connection 115 Vac
SITRAD
D2
A
B
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
D1/S3
TC-900
DIGITAL CONTROLLER FOR FREEZING SYSTEMS
WITH DEFROST SCHEDULING AND INTERNAL
DATALOGGER
Fast
Functions
Control
Luminosity
Hourmeter
Freezing
lockdown
functions
sensor
shutdown
e
TC-900
Log
is equipped with 3 relays (Comp,
TC-900E Log: 115 or 230Vac ±10% (50/60Hz)
TC-900EL Log: 12 or 24Vac/dc +10%
-50°C to 105°C / -58°F to 221°F
0 to 50°C / 32 to 122°F
COMP: 12(8)A / 240Vac 1HP
DEFR: 10A / 240Vac 2400W
FANS: 5(3)A / 240Vac
1.5 VA
10 to 85 %RH (without condensation)
76 x 34 x 77 mm (WxHxD)
71 ± 0,5 x 29 ± 0,5 mm (see item 5)
Functions lockdown indication LED
Control functions shutdown indication LED
Temperature unit indication LED
Log
71
± 0,5
mm
Dimension of the clipping
for fixing of the
instrument in panel
Panel
(Side View)
Panel (Front View)
Connection 230 Vac
SITRAD
D2
A
B
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
115 Vac
D1/S3
e
Log
IP 65
LOG
FRONT
Serial
Datalogger
Supervisory
Protection
Protocol
programming
system
level
Modbus
Connection 12 Vac/dc
SITRAD
D2
A
B
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
12 Vac/dc
D1/S3
The sensor S1 must be in the ambient.
The sensor S2 must be placed in the evaporator
through metallic cramp.
6. OPERATIONS
6.1 Quick Access Menu Map
To access or navigate the quick access menu using the
displaying the temperature. For every touch, the next function in the list is displayed. To confirm, use
/
the
(short press) key.
FAST FREEZING (ON/OFF)
;
ECONOMIC SETPOINT (ON/OFF)
;
DEFROST (ON/OFF)
;
FUNCTIONS LOCKDOWN
;
CONTROL FUNCTIONS
SHUTDOWN (ON/OFF)
;
Upper key
PRESET SELECTION
Lower key
;
NORMAL SETPOINT
;
6.2 Quick access keys map
When the controller is on temperature display, the following keys serve as a shortcut for the following
functions:
/
Hold down for 2 seconds: setpoint adjustment.
/
Hold down for 4 seconds: preset selection.
/
Short touch: the current day, month, year, day of the week, hour, and
minute will be shown in sequence on the display.
<
Short touch: displays the current process.
<
Hold down for 2 seconds: inhibits the audible alarm.
Hold down for 2 seconds: resets the counter when the hour meter is being
<
displayed.
<
Short touch: displays the maximum and minimum measurements recorded.
<
Hold down for 2 seconds: clears history when records are displayed.
<
Hold down for 4 seconds: carries out manual defrost.
;
Short touch: enter the quick access menu.
;
Pressed for 5 seconds: turn on/turn off the control functions.
<
<
Hold down for 10 seconds: manual datalogger activation.
and
<
<
and
Short touch: Go to menu selection.
230 Vac
evolution
e
e
Lo g
Lo g
TC -9 00
TC -9 00
COMPONENT
E251415
Connection 24 Vac/dc
SITRAD
D2
A
B
5
6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
Loads supply
24 Vac/dc
D1/S3
To the terminal
LEGEND:
the connecting block
;
(short press) key while the controller is
RESET HIGH AND LOW
EXIT FUNCTION
PRESSURE ALARMS
;
;
FUNCTION SELECTION
;
ON/OFF DATA LOGGER
(MANUAL MODE)
;
DATE AND TIME SETTING
;
DISPLAY HOURMETER
;
ERASE MIN. AND MAX.
VALUES
;
MIN. AND MAX.
TEMPERATURE RECORD
ECONOMIC SETPOINT
;
;
Loads supply
of

Advertisement

loading

Summary of Contents for Full Gauge Controls TC-900E Log

  • Page 1 3. TECHNICAL SPECIFICATIONS RESET HIGH AND LOW FAST FREEZING (ON/OFF) EXIT FUNCTION PRESSURE ALARMS TC-900E Log: 115 or 230Vac ±10% (50/60Hz) Power supply TC-900EL Log: 12 or 24Vac/dc +10% Control temperature -50°C to 105°C / -58°F to 221°F Operating temperature 0 to 50°C / 32 to 122°F...
  • Page 2 6.3 Basic Operations 6.3.6 How to determine the end of defrost by temperature a)Reconfigure the functions related to the end of defrost to the maximum value: 6.3.1 Operating mode - Time in refrigeration (interval between defrosts) F08 = 999min. This controller is able to operate in two different modes: - Evaporator temperature to end the defrost F13 = 105°C / 221°F Basic mode: It has 30 functions, in addition to defrost schedule and datalogger features.
  • Page 3 c)Browse the menu using the keys<or>until the option [Prog] appears, and then press/. 6.3.12 Hourmeter d)Use the keys <or>to select the day of the week to create the defrost schedule and press/. The hourmeter indicates the number of working hours of the compressor. The hourmeter can be viewed e)Again use the keys<or>to select which of the eight available defrosts will be configured and through the quick access menu (;) in the option [Hour] and the working time of the compressor is press/.
  • Page 4 6.5 Table of parameters CELSIUS (°C) FAHRENHEIT (°F) Description Unit Default Unit Default [,F00] Controller's operating mode [,F01] Defrost by hour programming [,F02] Control differential (normal hysteresis) °C °F [,F03] Minimum setpoint allowed to the end user °C °F [,F04] Maximum setpoint allowed to the end user °C °F...
  • Page 5: Description Of Parameters

    CELSIUS (°C) FAHRENHEIT (°F) Description Unit Default Unit Default [,F73] 0(NO) 1(YES) 0(NO) 0(NO) 1(YES) 0(NO) Enable second defrost output [,F74] Enable preset SP2 0(NO) 1(YES) 0(NO) 0(NO) 1(YES) 0(NO) [,F75] Enable preset SP3 0(NO) 1(YES) 0(NO) 0(NO) 1(YES) 0(NO) [,F76] Enable preset SP4 0(NO)
  • Page 6 F22 - Fan stop due to high temperature in the evaporator: F45 - Condition to start the defrost (0 - time / 1 - temperature): This aims at switching off the evaporator fan until the evaporator temperature approaches the It defines the condition to start the defrost: temperature provided in the project design, thus avoiding high suction pressures and temperatures that [,,,0]- Time could damage the compressor.
  • Page 7 F58 - Function of the digital input 2: F70 - Time to inhibit the reading of the low pressure when initializing: [Off,]Off Delay time that the suction line pressure switch takes to be within its ideal initialize the controller, [,,,1]Digital input: Activate economic setpoint (NO switch) avoiding unwanted alarms.
  • Page 8: Environmental Information

    - The product is violated or repaired by any person not a member of the technical team of The TC-900e Log allows you to configure the RS-485 communication port for the MODBUS-RTU protocol. For more information about the Full Gauge Controls;...