DCA-45SSIU3 (60 Hz) — OUTPUT TERMINAL PANEL CONNECTIONS
UVWO Terminal Output Voltages
Various output voltages can be obtained using the Output
Terminal Lugs .. The voltages at the terminals are depen-
dent on the position of the Voltage Selector Switch and the
adjustment of the Voltage Regulator Control Knob .
Remember the voltage selector switch determines the range
of the output voltage. The voltage regulator (VR) allows the
user to increase or decrease the selected voltage.
3Ø 240/139 Output Terminal Lug Voltages
1. Place the voltage selector switch in the 3Ø 240/139
position as shown in (Figure 22).
Figure 22. Voltage Selector Switch 240/139V
Three-Phase Position
2. Connect the load wires to the Output Terminal Lugs as
shown in (Figure 23).
Figure 23. Output Terminal Lugs
3Ø 240/139V Connections
3. Turn the voltage regulator knob (Figure 24) clockwise to
increase voltage output, turn counterclockwise to
decrease voltage output.
Figure 24. Voltage Regulator Knob (139V/240V)
PAGE 28 — DCA-45SSIU3 (60 HZ) — OPERATION MANUAL — REV. #2 (03/19/24)
3Ø 208V/1Ø120V Output Terminal Lug Voltages
1. Place the voltage selector switch in the 3Ø 240/139
position as shown in Figure 25.
2. Connect the load wires to the Output Terminal Lugs as
shown in Figure 26.
Figure 26. Output Terminal Lugs
3Ø-208V/1Ø120V Connections
3. Turn the voltage regulator knob (Figure 25) clockwise to
increase voltage output, turn counterclockwise to
decrease voltage output.
NOTE
Use this position for
3Ø-208 or 1Ø120V.
Figure 25. Voltage Selector
Switch 240/139V
Three-Phase Position
To achieve a 3Ø 208V output
the voltage selector switch
must be in the 3Ø-240/139
position and the voltage
regulator must be adjusted to
208V.