ABB ACS530-04 Hardware Manual page 85

Drive modules
Table of Contents

Advertisement

Notes:
1. Current [0(4)...20 mA, R
in
changing the corresponding parameter.
2. Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V) minus the power
taken by the option modules installed on the board.
5)
In sclar control (default): See Menu - Primary settings - Start, stop, reference - Constant frequencies or
parameter group 28 Frequency reference chain.
In vector control: See Menu - Primary settings - Start, stop, reference - Constant speeds or parameter
group Speed reference selection
DI3
DI4
Operation/Parameter
0
0
Set frequency through AI1
1
0
28.26 Constant frequency 1
0
1
28.27 Constant frequency 2
1
1
28.28 Constant frequency 3
6)
See Menu - Primary settings - Ramps or parameter group 28 Frequency reference chain.
DI5 Ramp set
Parameters
0
1
28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
1
2
28.74 Freq acceleration time 2
28.75 Freq deceleration time 2
5)
Connected with jumpers at the factory.
6)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the grounding shelf for the
control cables.
Further information on the usage of the connectors and switches is given in the sections
below.
Switches
Switch
TERM
Drive-to-drive link termination. Must be set to the terminated
(ON) position when the drive (or another device) is the first or
last unit on the link.
BIAS
Switches on the biasing voltages to the bus. One (and only
one) device, preferably at the end of the bus must have the
bias on.
= 100 ohm] or voltage [0(2)...10 V, R
Description
Installation instructions 85
> 200 kohm]. Change of setting requires
in
Position
Bus not terminated
ON
(default)
TERM
Bus terminated
ON
TERM
Bias off (default)
ON
BIAS
Bias on
ON
BIAS