Electrical installation
Warnings
WARNING! Obey the instructions in chapter
ignore them, injury or death, or damage to the equipment can occur. If you are not
a qualified electrician, do not do electrical work.
Make sure that the drive is disconnected from the input power during installation. If
the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
Necessary tools and instructions
•
Screwdriver and a set of suitable bits
•
Cabling tools
Terminal designations
For more detailed information on the connectors, see section
Relay outputs
Marking
50
RO4C
51
RO4A
52
RO4B
53
RO5C
54
RO5A
55
RO5B
115/230 V inputs
Marking
70
HDI7
71
HDI8
72
NEUTRAL
73
HDI9
74
HDI10
75
NEUTRAL
76
HDI11
77
HDI12
78
NEUTRAL
1)
Neutral points 72, 75 and 78 are connected.
General cabling instructions
Obey the instructions given in chapter
page 51.
Wiring
Connect the external control cables to the applicable module terminals. Ground the outer
shield of the cables 360 degrees under a grounding clamp next to the control unit.
Description
Common, C
Normally closed, NC
Normally open, NO
Common, C
Normally closed, NC
Normally open, NO
Description
115/230 V input 1
115/230 V input 2
Neutral point
115/230 V input 3
115/230 V input 4
Neutral point
115/230 V input 5
115/230 V input 6
Neutral point
Guidelines for planning the electrical installation
Optional I/O extension modules 155
Safety instructions
on page 13. If you
Technical data
on page 164.
on