Motor thermistor connection example
1)
1) One or 3...6 PTC thermistors connected in series.
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and
wiring are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-
02 PTC terminal.
Relay output connection example
RO PTC C
62
63
RO
PTC B
X4
OUT1
34
OUT2
35
SGND
36
IN1
37
IN2
38
Power supply connection example
1)
1) External power supply, 24 V AC/DC
WARNING! Do not connect the +24 V AC cable to the control unit ground when
the control unit is powered using an external 24 V AC supply.

Start-up

Setting the parameters

1. Power up the drive.
2. If no warning is shown,
make sure that the value of both parameter 15.02 Detected extension module and
parameter 15.01 Extension module type is CMOD-02.
60
61
CMOD-02
CCU
+
24V AC/DC + in
40
24V AC/DC - in
-
41
CMOD-02
Optional I/O extension modules 169
PTC IN
PTC IN
CMOD-02