Motor thermistor connection example
1)
1) One or 3...6 PTC thermistors connected in series.
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and
wiring are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-
02 PTC terminal.
Relay output connection example
RO PTC C
62
63
RO
PTC B
X4
OUT1
34
OUT2
35
SGND
36
IN1
37
IN2
38
Power supply connection example
1)
1) External power supply, 24 V AC/DC
WARNING! Do not connect the +24 V AC cable to the control unit ground when
the control unit is powered using an external 24 V AC supply.
Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameter 15.02 Detected extension module and
parameter 15.01 Extension module type is CMOD-02.
60
61
CMOD-02
CCU
+
24V AC/DC + in
40
24V AC/DC - in
-
41
CMOD-02
Optional I/O extension modules 169
PTC IN
PTC IN
CMOD-02