Carrier 48FC 08-16 Series Service And Maintenance Instructions page 42

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

8.
Disconnect a gas pipe union and remove the gas manifold
with the gas valve.
9.
Remove the two screws attaching the burner rack to the
vestibule plate (see Fig. 56).
10. Remove the pressure switch hose from the connection on
the flue cover assembly (see Fig. 56).
11. Remove the screws around the vestibule plate.
SPARK GAP
.120/.141 IN. (3.05/3.56 mm)
DETAIL "A"
Low Heat
Medium Heat
High Heat
SPARK GAP MUST BE POSITIONED TO
IGNITE ON FIRST TRY. (PLACE
SPARK GAP WITHIN BURNER
CIRCUMFERANCE AS SHOWN)
Fig. 61 — Spark Adjustment
12. Remove the nuts holding the heat exchanger support rack
to the fan deck.
13. Remove the heat exchanger from the unit.
14. Separate the following from the heat exchanger: inducer
fan-motor assembly, flue cover assembly, retainer, regula-
tor, and regulator gasket. See Fig. 56.
See
Detail "A"
See
Detail "A"
See
Detail "A"
42
See
Detail "B"
See
Detail "B"
See
Detail "B"
.200 IN. (5.07 mm)
DETAIL "B"