Reinstalling Motor and Fan Assembly
See Fig. 18.
1.
Align motor harness/grommet at ~7 o'clock (facing
installer) and align the bottom flats on right and left sides
of fan stator with fan deck ribs. Drop fan assembly down
into fan deck opening and slide back until aluminum stator
is under the rear fan deck brackets.
2.
Replace four front brackets and secure each with 2 #10 x
5/8-in. hex head screws (P/N: AL48AM217). Tighten to
50 in.-lb (5.65 Nm).
3.
Reconnect wires for stator temperature limit switch.
4.
Pull motor harness tight through grommet and plug it in to
the control box harness and secure in the corner with snap-
in wire tie.
4
3
2
Fig. 18 — Fan Assembly Installation
1
12