Carrier 48FC 08-16 Series Service And Maintenance Instructions page 124

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 7.5 to 15 nominal tons
Table of Contents

Advertisement

PRESSURES
Gas Inlet Pressure in. wg
Gas Manifold Pressure
Refrigerant Suction
Refrigerant Discharge
Verify Refrigerant Charge using Charging Charts
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped)
Verify smoke detector unit shutdown by utilizing magnet test
Verify outdoor fan operation. On units with head pressure controls, verify outdoor fan ramps up
IV. HUMIDI-MIZER® SYSTEM START-UP
STEPS
1. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure
B. Discharge pressure
C. Entering air temperature
D. Leaving air temperature
2. Switch unit to mixed cool and reheat mode (subcool)
OBSERVE
A. Reduction in suction pressure (5-7 psi expected)
B. Discharge pressure unchanged
C. Delta temperature decreases, close to neutral air
3. Switch unit to hot gas reheat mode
OBSERVE
A. Suction pressure increases to normal cooling level
B. Discharge pressure decreases (35-50 psi) (Limited by head pressure control)
C. Liquid temperature returns to normal cooling level
4. With unit in dehumid mode switch to heating and verify compressor and outdoor fan stop
5. Turn off heating, cooling, and reheat, restore set points for thermostat and humidistat
© 2023 Carrier
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480332-01
_____________ in. wg
STAGE 1
_____________ in. wg
STAGE 2
_____________ in. wg
_____________ PSIG
_____________ PSIG
Printed in U.S.A.
Form 48FC-8-16-01SM
_______________ PSIG
_______________ PSIG
_______________ ° F
_______________ ° F
Pg CL-2
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
(Y/N) _____
11-23
Replaces: NEW

Advertisement

Table of Contents
loading

Table of Contents