2: Installer Manual; System Overview - Danfoss GX-850M Installation Instruction

Automatic control panel ver. iv
Table of Contents

Advertisement

Installation Instruction
2.
Installer Manual

System overview

The GX-850M ver. IV can handle up to 2 independent areas, in any of the following combinations:
Single roof system
(1 system, 1-4 roof sensors)
Single ground system
(1 system, 1-4 roof sensors)
1 ground system and 1 roof system (combi system)
(2 systems, 2-4 sensors total, minimum 1 sensor per system)
2 roof systems (dual system)
(2 systems, 2-4 sensors total, minimum 1 sensor per system)
2 ground systems (dual system)
(2 systems, 2-4 sensors total, minimum 1 sensor per system)
When more than 1 area is controlled by the GX-850M ver. IV system, it is also possible to prioritize the
areas. Prioritizing makes it possible to operate 2 areas, even if the needed power for 2 areas is not pre-
sent.
A typical ice and snow melting system consists of:
GX-850M ver. IV
Only 1 GX-850M ver. IV is allowed on the Devibus™
Power supply
More power supplies can be connected in parallel (if needed)
Be aware of maximum number of sensors on each power supply
(Refer to Technical Specification for power demand of sensors)
Ground and/or roof sensor(s)
• Be aware of maximum number and cable length of sensors on each power supply
(Refer to sensor manual for a more detailed description)
10 | © Danfoss | 2018.10
GX-850M ver. IV
VUAPA422