6.5.4 Monitoring Device Terminal

The WIT inverter is equipped with a USB port that allows for remote monitoring when
connected to a monitoring device, such as a USB-to-WiFi module, ShineWiFi-X, Shine4G-
X, ShineLan-X, and others. Additionally, you can perform software updates using a USB
flash drive.
1. Remove the waterproof cover from the USB port.
2. Insert the USB-to-WiFi module, ensuring that the triangle icon is facing upward, and
then secure it by tightening the screw, as shown in Fig 6.14. If the module is working
properly, its LED indicator will light up.
NOTE: Before you leave, please ensure that the monitoring device is removed and the
protective cover should be reinstalled to avoid any water damage.
1
Fig 6.14 Connecting the monitoring device

6.5.5 DRMS Port

The WIT inverter comes with a DRMS port. Users can choose to connect to this terminal if
required by local regulations. The connection procedure is as follows:
1. Connect the communication cable to the port as required. The DRMS port is a standard
RJ45 connector, so you can establish a connection following the typical Ethernet wiring
method.
2. Remove the dustproof cover from the DRMS port and check whether there is a
waterproof silica gel pad. Insert the cable and tighten the rubber ring to prevent any
loose connections.
3. Once the cable connection is complete, reinstall the dustproof cover.
Table 6.8 describes the DRM requirements.
41
2
1
Route the cable
2
Strip the cable
15±1mm
3
Crimp the cable
4
Tighten the terminal
Fig 6.15 DRMS port
Table 6.8 Demand Response Modes (DRMs)
Socket asserted by
Mode
shorting pins
DRM0
5, 6
DRM1
1, 6
DRM2
2, 6
Do not consume at more than 50% of rated power
Do not consume at more than 75% of rated power AND
DRM3
3, 6
Increase power consumption (subject to constraints
DRM4
4, 6
DRM5
1, 5
DRM6
2, 5
Do not generate at more than 50% of rated power
Do not generate at more than 75% of rated power AND
DRM7
3, 5
Increase power generation (subject to constraints from
DRM8
4, 5
Open the cover
5
Cover
Connect to the terminal
6
A
A
A-A
Requirement
Operate the disconnection device
Do not consume power
Source reactive power if capable
from other active DRMs)
Do not generate power
Sink reactive power if capable
other active DRMs)