Page 1
Installation, Use and Maintenance Manual for model R1K 28 RAIN Premix condensing system boiler only heating, suitable for outdoor installation 0476 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› (See chap “chapter name”): this entry indicates another section in the Manual that you should refer to. › Device: this term is used referring to the boiler. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 5
PRODUCT CONFORMITY These gas boilers comply with the European Directives and with the requirements provided in the European standards below: › Eco-design Directive 2009/125 CE, R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
1. INSTALLER SECTION 1. INSTALLER SECTION The installation operations described in this section should be performed only by qualified personnel, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
1.1.3. REFERENCE LEGISLATION The installation must be realized according to the requirements of current legislation and in compliance with local technical regulations, according to the indications of the good technique. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› Turn the boiler at 90° holding it with your hand (fig. 1-B). › Lift the box (fig. 1-C) and remove the guards (fig. 1-D). fig. 1 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
(see fig.1) so as to allow the condense to drain. fig.1 1.1.8. CIRCULATOR PREVALENCE/ FLOW DIAGRAM Wilo-Yonos PARA MSL 12/6B p/kPa Q/m³/ h Q/l/s Q/Igpm max. Q/m³/ h Appliance Loss R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
25 °f. However, please check the characteristics of the water used and install suitable treating devices. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
“M” (fig. 2) to make sure that the system pressure reaches 1.2 bar (fig. fig. 2 after performing this operation, make sure that the loading tap “R” (fig. 2) is properly closed. fig. 3 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› Connect the dedicated flexible condensate draining tube to a waste disposal system. The condensate can be drained directly in the sewerage system by inserting an easily serviceable siphon. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
If the temperature goes below -10° centigrades, please fill the plant with anti-freeze liquid (CLEANPASS FLUIDO AG cod. 98716LA) and insert and electrical resistances kit (cod. 82259LP). R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
WARNING It is strictly forbidden the use of adaptors, multiple plugs and/or extensions for the general power supply of the equipment from the electrical network. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
· the blue cable to the terminal marked with “N”. · the brown cable to the terminal marked with “L”. After performing these operations, remount plate “A” and the front casing. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
‘ ’. After performing these operations, remount plate “A” and the front casing. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 21
TAZ1: ENVIRONMENT THERMOSTAT AREA 1 ORANGE TAZ 2: ENVIRONMENT THERMOSTAT AREA 2 BLACK VZ1: AREA 1 VALVE BROWN VZ2: AREA 2 VALVE LIGHT BLUE VZR: REMOTE CONTROLLED AREA VALVE R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 22
‘5’ (see chapter ‘DIGITECH CS PARAMETERS TABLE’), the burner ignition request in heating mode is disabled, when closing the contact (even if the request comes from a connected room thermostat or remote control). R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› Make sure that the discharge tube doe not protrude inside the fumes exhaust duct, stop before it reaches the inner surface of the latter. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
· have the axis of the inlet end perpendicular to the internal wall opposite to the chimney or fume exhaust duct; R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 25
50% the section of the vents. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Subsequent addition of a curve is similar to adding a linear length of tube according to the indications below: co-axial curve Ø80 to 90° = 1.5 m co-axial curve Ø80 to 45° = R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 27
Subsequent addition of a curve is similar to adding Ø80 a linear length of tube according to the indications below: co-axial curve Ø80 to 90° = 1.5 m co-axial curve Ø80 to 45° = R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 28
1 PLEASE NOTE: during the flue analysys tests, place the analyser inside the frontal flue kit terminal slots ‘F’ (fig. fig. 2 SECTION A-A R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
1. SUPPORT CENTRE SECTION 2. SUPPORT CENTRE SECTION All operations described below relative to first start- up, maintenance and replacement should be performed only by qualified personnel...
Local and National Laws and Standards; › make sure that the heating system gate valves are open; › make sure that there is no intake of gaseous products within the system; R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› If the flame is missing, the board will repeat the start-up operations after post-ventilation (20 seconds). › You might have to repeat the start-up operation several times to release all the air inside the gas R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› After each adjustment variation on screw ‘1’ (fig. 2) of the gas flow adjuster you have to wait for the boiler to stabilize itself to the set value (about 30 seconds). R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
’with the message ‘P00’, and release the keys ‘ ’ and ‘ ’. Use the keys ‘ ’ and ‘ ’ of the heating circuit to select the parameter to be edited. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 34
To exit the parameters menu, hold at the same time the keys ‘ ’ and ‘ ’ and wait for the symbol ‘ ’ to appear on the display. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
0 - 5 0 = ISTANTANEOUS R2K 1 = ISTANTANEOUS RKR 2 = ACCUMULATION IN CALDAIA 3 = ACCUMULATION REMOTO 4 = ISTANTANEOUS COMFORT - FAST H2O 5 = HEATING ONLY R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 36
MULTIPLES OF 5 SECONDS TIME FOR WHICH THE BURNER WILL BE TURNED OFF ONCE (PRE-SET AT 36 X 5 = 180 THE HEATING TEMPERATURE REACHED THE USER SET SECONDS) TEMPERATURE. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 37
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE ELECTRIC FAN PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER F R E Q U E N C Y P02) (HZ)’ R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 38
HOT WATER TREATMENT (AND INFORM THE USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS, ANIMALS AND PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED AT THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 39
Tm (°C) Kd = 25 Kd = 30 Kd = 20 45 MAX Kd = 15 Kd = 10 Kd = 5 Kd = 0 25 MIN Te (°C) R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 40
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED) THROUGH THIS PARAMETER YOU CAN SET THE TEMPERATURE 10 - 40 THE VALUE IS EXPRESSED IN °C DIFFERENCE BETWEEN DELIVERY AND RETURN. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 41
3 = 4800 4 = 9600 5 = 19200 MODBUS MODE 0 - 2 0 = ENABLED 1 = ENABLED WITH LOCAL SETTINGS 2 = DISABLED (SET BY DEFAULT) R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 43
ELECTRICAL CONNECTIONS”) 1 = AIR PRESSURE-SWITCH THIS PARAMETER IS AUTOMATICALLY SET TO THE VALUE ‘1’ SAFETY WHEN THE VALUE OF PARAMETER P00 IS SET TO ‘11’. 2 = TELEPHONE DIALER R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
2. FIRST START-UP 2.1.6. ELECTRIC FAN FREQUENCY/HEAT CAPACITY DIAGRAM FREQUENCY (Hz) STARTING STEP GAS TYPE MINIMUM FREQUENCY MAXIMUM FREQUENCY ADJUSTMENT R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› remove and clean the burner from oxidation; the internal system. › check the integrity and the position of the sealed chamber sealing gasket; R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Fumes mass - Heat Input min. 1,78 NOx class class Weighted NOx (0% O2) ppm Weighted NOx (0% O2) mg/kWh mg/kWh Central heating circuit Temperature setting - Central heating °C 30-80 / 25-45 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 47
Max. Flue length Ø60 - Vert. Pipe Max. Flue length Ø80 - Vert. Pipe Electrical specifications Voltage-frequency V/Hz 220-230/50 Nominal power consumption 0,75 Electric power with boiler OFF Max Power consumption R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 48
Supply pressure min. - G31 mbar Supply pressure max. - G31 mbar Fan speed Max. HEATING output - G31 Fan speed Min. HEATING output - G31 Gas consumption - G31 kg/h 2,17 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 49
At rated heat output of cogeneration space heater with CHP100+Sup100 Rated heat output Psup Type of energy input Other items Standby heat loss P stby Ignition burner power consumption P R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 50
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet. (**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet). R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
TA: ENVIRONMENT THERMOSTAT AR: ORANGE VG: GAS VALVE SR: HEATING PROBE L: LINE GI: YELLOW TRA:START-UP TRANSFORMER EV: ELECTRIC FAN N: NEUTRAL BI: WHITE SRI: RETURN SENSOR NE: BLACK GR. GREY R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› remove the fastening screws (5) placed on the front edge of the side panel; › grab the bottom of the panel, and remove it by moving it sideways and pulling it upwards. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
(fig. 1) loosening them and turn the panel downwards; › unscrew the four fastening screws 1 - fig. 1; › remove the crankcase pulling it upwards. fig. 1 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
› close the main supply tap of the water supply network; › open all cold and hot water taps; › after completing all operations, close the discharge tap and all previously opened water taps. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
IF THE TENSION MEASURES BETWEEN PHASE-PHASE NEUTRAL AND GROUND IS ALMOST EQUAL TO THE ONE MEASURED BETWEEN PHASE AND GROUND, YOU HAVE TO INSTALL A PHASE-PHASE TRANSFORMER KIT (COD. 88021LA) R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 58
SWITCH CHECK THE WIRING; MANUAL RESET CABLE DISCONNECTED; (PRESS THE RESET ‘ ’ KEY). DISCHARGE OR SUCTION CHECK THE FUMES DISCHARGE DUCT; CLOSED; AIR PRESSURE SWITCH REPLACE IT. DEFECTIVE. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 59
REMOTE CONTROL IS NOT COMPATIBLE WITH THE P.C.B. COMMUNICATION ERROR NO ELECTRICAL CHECK THE WIRING; AUTOMATIC. BETWEEN THE BOILER CONNECTION; BOARD AND THE MODBUS BOARD MODBUS BOARD BROKEN; REPLACE IT; R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 60
SUPPLY VOLTAGE FALLS BACK WITHIN THE REQUESTED LIMITS). COMMUNICATION FAULT NO ELECTRICAL CHECK THE WIRING; AUTOMATIC. BETWEEN MODBUS CONNECTION; CONTROLLER AND MODBUS CONTROL UNIT MODBUS CONTROL UNIT REPLACE IT; BROKEN. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
IT CAN ALSO ACTIVATE DURING NORMAL BOILER OPERATION, IF THE WATER PRESSURE SWITCH CONFIRMATION IS MISSING, WHEN THE CONTACT IS RE-CLOSED, A 2 MINUTES RELEASE CYCLE WILL BE PERFORMED. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
3 (see chapters ‘DIGITECH CS PARAMETERS TABLE’ and ‘ACCESSING AND PROGRAMMING THE PARAMETERS’); › adjust the CO2 combustion value as indicated in chapter ‘CO2 VALUE CHECK AND CALIBRATION’. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
1. USER SECTION 3. USER SECTION The operations described in this section are addressed to all those who will use the machine. The machine must be used and accessed only by qualified operators that fully read and understood the User section, paying particular attention to the warnings.
DANGER If you sense a gas odour in the location in which the boiler is installed, proceed as follows: R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
SWEEP FUNCTION ACTIVATION (HOLD FOR 7 SECONDS) VALUE OF THE PARAMETERS ADJUSTMENT KEY / HOLD THE KEYS AT THE SAME TIME FOR 5 SECONDS TO ACTIVATE DISPLAY BACK LIGHT FOR 10 MINUTES R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
MODULATING POWER LEVEL OF THE BOILER (fig.2) 11. ERROR DISPLAY THAT CAN BE RESET 12. OFF OPERATING MODE 13. ERROR DISPLAY THAT CAN NOT BE RESET 14. OPERATION IN HEATING MODE ENABLED R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
OF THE REMOTE TANK TO THE BOILER (ONLY FOR HYBRID DOMESTIC SYSTEM WITH OPTIONAL SENSOR) POWER SUPPLIED BY THE HEATING PUMP IN KW/H (ONLY FOR HYBRID DOMESTIC SYSTEM) HEATING FLOW RATE DISPLAY EXPRESSED IN L/MIN (IF THERE IS A FLOWMETER). R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
30 °C to 80 °C (25 °C – 45 °C for floor systems). OFF MODE In this mode the boiler no longer meets the heating demands, the anti-freeze and pump anti-locking systems still remain active. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
This function is available only if: › the boiler is powered; › the gas supply is open; › the pressure of the system is proper; › the boiler is not blocked. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
2 minutes system relief cycle. Throughout this function the display will fig. 1 show the code “F33”. The boiler can work normally only after completing the operation. fig. 2 R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
CUT OFF THE POWER SUPPLY FROM THE MAIN SWITCH AND THEN RESTORE IT, AS SOON AS THE ERROR CODE DISAPPEARS, THE BOILER WILL RESTART AUTOMATICALLY. IF THE BLOCK PERSISTS CONTACT THE TECHNICAL SUPPORT CENTRE. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Page 72
FROM THE DISPLAY, THE BOILER WILL START AUTOMATICALLY. SUPPLY VOLTAGE CONTACT THE TECHNICAL SUPPORT CENTRE. COMMUNICATION FAULT BETWEEN CONTACT THE TECHNICAL SUPPORT CENTRE. MODBUS CONTROLLER AND MODBUS CONTROL UNIT R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
H E A T I N G WAIT UNTIL A N T I - F R E E Z E OPERATION IS COMPLETED FUNCTION ACTIVE SYSTEM WAIT UNTIL RELEASE CYCLE OPERATION IS COMPLETED IN PROGRESS R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
(Waste Electrical and Electronic Equipment) shows that this product can not be dismantled as domestic waste. Proper dismantle of this product helps preventing potentially negative consequences on human health and environment. R1K 28 RAIN - RAD - ING - Manuale - 2103.1_SKB1.3_v.28_kW_firm.L224G...
Need help?
Do you have a question about the R1K 28 RAIN and is the answer not in the manual?
Questions and answers