Simultaneous Welding And Auxiliary Power Loads - Lincoln Electric RANGER 305 D Service Manual

Hide thumbs Also See for RANGER 305 D:
Table of Contents

Advertisement

RANGER 305D
The 240 VAC receptacle can be split to provide two separate120 VAC
outputs with a maximum permissible current of 42 amps pea, 40
amps continuous per outlet to two separate 20 amp branch circuits.
(These circuits cannot be paralleled.) Output voltage is within +/-
10% at all loads up to rated capacity.
The 120 V auxiliary power receptacles should only be used with
three-wire, grounded type plugs or approved double insulated tools
with two-wire plugs. The current rating of any plug used with the
system must be at least equal to the current capacity of the
associated receptacle. For extension cord lengths, see Table B.5.
NOTE: The 240 VAC receptacle has two circuits, each of which
measure 120 VAC to neutral. However, they are of opposite polarities
and cannot be paralleled.
WELDING
OUTPUT-AMPS
AT NEMA ARC-VOLTS
0
100
150
200
250
300
* Each 120 VAC leg of the 120/240 VAC Full KVA receptacle can deliver a maximum
40 amps, up to a total of 80 amps at 9500 Watts, 60 amps at 7100 Watts, or 46
amps at 5600 Watts. These outputs cannot be paralleled, so the greatest single
120 VAC load is 40 amps.
Each 120 VAC Duplex receptacle is limited to 20 amps maximum.
TABLE B.5 - RANGER 305D EXTENSION CORD LENGTH RECOMMENDATIONS
(USE THE SHORTEST LENGTH EXTENSION CORD POSSIBLE SIZED PER THE FOLLOWING TABLE.)
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
30
20
120
2400
15
240
3600
60
20
240
4800
33
240
8000
RANGER 305D SIMULTANEOUS WELDING AND POWER LOADS
PERMISSABLE AUXILLARY
POWER-WATTS
(UNITY POWER FACTORY)
9500
7100
5600
4500
2800
0
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
(9)
40
(12)
30
(9)
(18)
75
(23)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
SIMULTANEOUS WELDING AND
AUXILIARY POWER LOADS
The above auxiliary power ratings are with no welding load.
Simultaneous welding and power loads are specified in Table B.4. The
permissible currents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the same time).
PERMISSABLE AUXILIARY
CURRENT IN -AMPS @
120 VAC*
40*, (42* PEAK)
40*
40*
32
16
0
10 AWG
8 AWG
75
(23)
125
(38)
50
(15)
88
(27)
150
(46)
225
(69)
100
(30)
175
(53)
60
(18)
100
(30)
B 9
OPERATION
240 VAC
40, (42 PEAK)
30
23
16
8
0
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
225
(69)
350
(107)
600
(183)
275
(84)
450
(137)
175
(53)
250
(76)

Advertisement

Table of Contents
loading

Table of Contents