Arc Gouging; Auxiliary Power; Simultaneous Welding And Auxiliary Power Loads - Lincoln Electric Ranger 305LPG Operator's Manual

Hide thumbs Also See for Ranger 305LPG:
Table of Contents

Advertisement

B-6

ARC GOUGING

The RANGER® 305LPG can be used for limited arc
gouging. For optimal performance, set the MODE
switch to CC-STICK and the ARC CONTROL to +10.
Set the CONTROL knob to adjust output current to
the desired level for the gouging electrode being used
according to the ratings in the following table.
Carbon Diameter
1/8"
5/32"
3/16"

AUXILIARY POWER:

Start the engine and set the IDLER control switch to
the desired operating mode. Full power is available
regardless of the welding control settings providing no
welding current is being drawn.
The auxiliary power of the RANGER® 305LPG con-
sists of two 20 Amp-120 VAC GFCI (5-20R) duplex
receptacles and one 50 Amp 120/240 VAC (14-50R)
receptacle. The 240 VAC receptacle can be split for
single phase 120 VAC operation. See the "MAINTE-
NANCE SECTION" for detailed information on testing
and resetting the GFCI receptacle.
RANGER® 305LPG Simultaneous Welding and Power Loads
Welding
Output-Amps
0
100
150
200
250
300
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 40A per 120 VAC branch circuit when splitting the 240 VAC output.
RANGER® 305LPG Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current
voltam-
Load
(Amps)
meters
(Watts)
15
120
1800
20
120
2400
15
240
3600
20
240
4800
37
240
9000
OPERATION
Current Range
(DC, electrode Positive)
60-90 Amps
90-150 Amps
200-250 Amps
Permissible Power-Watts
(Unity Power Factor)
9000
7600
6500
5300
3800
1700
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
30
(9)
60
(18)
75
(23)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
RANGER® 305LPG
The auxiliary power capacity is 10,000 watts Peak,
9,000 Watts continuous of 60 Hz, single phase power.
The auxiliary power capacity rating in watts is equiva-
lent to volt-amperes at unity power factor. The max
permissible current of the 240 VAC output is 40 Amps.
The 240 VAC output can be split to provide two sepa-
rate 120 VAC outputs with a max permissible current
of 40 Amps per output to two separate 120 VAC
branch circuits (these circuits cannot be paralleled).
Output voltage is within ± 10% at all loads up to rated
capacity. All auxiliary power is protected by circuit
breakers.
The 120 V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs. The current
rating of any plug used with the system must be at
least equal to the current capacity of the associated
receptacle.
NOTE: The 240 V receptacle has two circuits, each of
which measure 120V to neutral but are of opposite
polarities and cannot be paralleled.

Simultaneous Welding and Auxiliary Power Loads

The above auxiliary power ratings are with no welding
load. Simultaneous welding and power loads are
specified in the following table. The permissible cur-
rents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the
same time).
Permissible
Current in
@120 VAC *
74**
70**
60**
50**
36
16
10 AWG
8 AWG
75
(23)
125
(38)
50
(15)
88
(27)
150
(46)
225
(69)
100
(30)
175
(53)
53
(16)
96
(29)
B-6
Auxiliary
-Amps
@ 240 VAC
37
35
30
25
18
8
6 AWG
4 AWG
175
(53)
300
(91)
138
(42)
225
(69)
350
(107)
600
(183)
275
(84)
450
(137)
160
(49)
239
(73)

Advertisement

Table of Contents
loading

This manual is also suitable for:

1266913173

Table of Contents