Problem
Refrigerant is leaking.

10 Warranty

The statutory warranty period applies. If the product is defective, please contact the manufacturer's branch in your
country (see dometic.com/dealer) or your retailer.
For repair and warranty processing, please include the following documents when you send in the device:
• A copy of the receipt with purchasing date
• A reason for the claim or description of the fault
Note that self-repair or nonprofessional repair can have safety consequences and might void the warranty.

11 Disposal

Recycling packaging material: Place the packaging material in the appropriate recycling waste bins wher-
ever possible.
Recycling products with batteries, rechargeable batteries, and light sources: Remove any batteries,
rechargeable batteries, and light sources before recycling the product. Return defective or used batteries
to your retailer or dispose of them at collection points. Do not dispose of any batteries, rechargeable bat-
teries, and light sources with general household waste. If you wish to finally dispose of the product, ask
your local recycling center or specialist dealer for details about how to do this in accordance with the ap-
plicable disposal regulations. The product can be disposed free of charge.
Disposal refrigerant: Provide the refrigerant in the correct recovery cylinder back to the refrigerant supplier with a
waste transfer bill. Do not mix refrigerants in the refrigeration systems and the cylinders.
If compressors or compressor oils are to be disposed of, ensure that the compressors have been evacuated to an ac-
ceptable level to ensure that no flammable refrigerant remains in the lubricant. To speed up the evacuation process,
the compressor housing must only be heated electrically. When draining oil from a system, ensure that it does not ig-
nite or come into contact with the ground.
28
Possible cause
The vacuum pump is defective.
The refrigerant circuit lines are not
properly welded.
Suggested remedy
Restart the vacuum pump (see
Draining the refrigerant
page 15).
Follow the manufactur's instruc-
tion.
Use an intact vacuum pump.
Isolate the leak in the refrigerant
circuit with isolation valves and
braze the defective refrigerant
circuit pipe.
Discharge the refrigerant and
restart the refilling process
(Draining the refrigerant
page 15 and
Filling the refrig
erant
on page 17).