[ IX Troubleshooting ]
[4]
Remove the wire for the out-
Check the fan
door fan motor, and check the
motor ground
fan motor megger and the
fault or the
winding resistance.
winding.
[5]
(1)
Check the fan
board failure.
(2)
(3)
HWE20010
Items to be checked
Check the fan output wir-
ing.
Check the connector
CNVDC/CNDCP connec-
tion.
Check the FAN board
failure.
Phenomena
1)
Fan motor megger failure
Failure when the megger is 1Mohm
or less.
2)
Fan motor disconnection
Standard: The winding resistance
is approximately several ohm.
(It varies depending on the tem-
perature, or while the inner thermo
is operating, it will be
Connector contact failure
Board side
Fan motor side
Cnnector contact failure
1)
The voltage imbalance among
each motor wiring during operation
(The voltage imbalance is greater
than the larger of the values repre-
sented by 5% or 5V.)
2)
The same error occurs even after
the operation is restarted.
- 128 -
Remedy
Replace the fan motor.
ohm)
Connect the connector.
Connect the connector.
Replace the FAN board.
GB