Gree GWH07AFAXA-K3NNA1A Service Manual page 64

Table of Contents

Advertisement

Service Manual
Note:
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with
expansion screws.
(1) Take sufficient protective measures when installing the
outdoor unit.
(2) Make sure the support can withstand at least four times the
unit weight.
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18)
(4) For the unit with cooling capacity of 2300W~5000W, 6
expansion screws are needed; for the unit with cooling capacity
of 6000W~8000W, 8 expansion screws are needed; for the unit
with cooling capacity of 10000W~16000W, 10 expansion screws
are needed.
At least 3cm above the floor
Fig.18
2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent.(As show in Fig.19)
3. Fix Outdoor Unit
(1) Place the outdoor unit on the support.
(2) Fix the foot holes of outdoor unit with bolts.(As show in Fig.20)
Foot holes
Foot holes
Fig.20
NOTE: When there're multiple cables passing
through it, the cross-hole of handle should be
knocked off and eliminate the sharp burrs for
avoid damaging the cables. Only applicable
for some models.
4. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle of outdoor unit and
then remove the handle. (As show in Fig.21)
(2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe. (As show in Fig.22)
Liquid
valve
Installation and Maintenance
Drain vent
Drain hose
Outdoor drain joint
Fig.19
Fig.21
cross-hole
Liquid pipe
Pipe joint
gas pipe
Union nut
gas valve
Fig.22
(3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
Refer to the following table for wrench moment of force:
5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire and
signal control wire (only for cooling and heating unit) to the wiring
terminal according to the color; fix them with screws. (As show in
Fig.23)
(2) Fix the power connection wire and signal control wire with
wire clip (only for cooling and heating unit).
Chassis
Fig.23
Note: the wiring connect is for reference only,please refer to
the actual one.
Note:
(1) After tightening the screw, pull the power cord slightly to check
if it is firm.
(2) Never cut the power connection wire to prolong or shorten the
handle
distance.
screw
6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. semidiameter of bending the pipe is
10cm.
(2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room. (As show in
Fig.24)
Note:
(1) The through-wall height of drain hose shouldnt be higher than
the outlet pipe hole of indoor unit.(As show in Fig.25)
Tightening torque (N . m)
Piping size (inch)
1/4
3/8
1/2
5/8
3/4
07K~18K
GWH24AADXE-K3NNA1A/O
N(1) 2
4
5
yellow-
blue black
violet
orange
green
Indoor unit connection
36K:
N(1) 2
3
L
N
brown brown
yellow-
blue black
blue
yellow-
(black)
green
green
L
N
POWER
Indoor unit connection
Wall
U-shaped curve
Drain hose
Fig.24
15~20
30~40
45~55
60~65
70~75
28K GWH24QE-K3NNB4G/O
N(1) 2
3
4
5
blue black brown violet
orange
yellow-
green
Indoor unit connection
The drain hose
can't raise
upwards.
Fig.25
61