Siemens SIMATIC ET 200SP Equipment Manual page 43

Interface module
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interrupts, diagnostics, error, and system messages
6.3 Alarms
Diagnostics alarm
Channel
Error
Type
(CET)
Configuration error:
0x0602
Invalid BusAdapter
on the interface
module
Load voltage error:
0x0610
Missing voltage in
load group at slot
according channel
number
The scope of the diagnostics alarms displayed depends on the configuration and the
parameter assignment.
If required, the standard can be downloaded from the Internet (http://www.profibus.com).
See also
PROFINET System Description
(http://support.automation.siemens.com/WW/view/en/19292127)
From PROFIBUS DP to PROFINET IO
(http://support.automation.siemens.com/WW/view/en/19289930)
Example application (http://support.automation.siemens.com/WW/view/en/24000238)
I/O modules (http://support.automation.siemens.com/WW/view/en/55679691/133300)
PROFINET with STEP 7 V11 (http://support.automation.siemens.com/WW/view/en/49948856)
42
Extended
Associated
Channel
value
Error
AddValue
Type
(ECET)
0x069C
-
0x6B0
-
Meaning / Cause
The installed BusAdapter
does not correspond to the
configuration.
No supply voltage to the
load group.
IM 155-6 PN ST Interface Module (6ES7155-6AU02-0BN0)
Equipment Manual, 11/2023, A5E53132379-AA
Remedy
Check project planning and
mounting of the correct
BusAdapter.
Check the load supply voltage
of the modules.