Technical data

Type
Power supply
Nominal current
Nominal force
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Nominal stroke length* ** See type plate
Additional functions **
* Adjustable with PLP 1
Running speed
and forces
Normal operation =
SHEV- fast running =
Forces
ZA-0300 ZA-0800 ZA-1000
OPEN
300 N
67.4 lbf
CR III
300 N
67.4 lbf
CR II
300 N
67.4 lbf
CR I
300 N
67.4 lbf

Entrapment protection

The drives were not evaluated for
entrapment protection.
In "CLOSE" direction the drive has an active
clamping protection for the main closing edge. With
an overload in the closing range 3 and 2 the drive
runs "OPEN" for 10 seconds, then drive "CLOSE"
again. If after three attempts a closing is not possible,
the drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s (0,2"/s). The drive were
not evaluated for entrapment protection.
99.824.45 3.1/03/22
ZA-0300 (-HS)
24 V DC, ±15 %
0,5 A (1.2 A)
300 N / 67.4 lbf
1100 N / 247.3 lbf
>20 000 double strokes
30 % (with cycle time 10 minutes)
Anodized aluminium / polycarbonate
IP 65 ("-W" = IP 54)
-5 ... +75 °C (23 ... 167 °F)
30 min / 300 °C (572 °F)
/
Closing edge protection activated (3 stroke repeatings)
** Programmable with Service and Configuration Suite (SCS)
800 N
1000 N
179.8 lbf
224.8 lbf
800 N
1000 N
179.8 lbf
224.8 lbf
800 N
1000 N
179.8 lbf
224.8 lbf
800 N
800 N
179.8 lbf
179.8 lbf
(see N.12 of Safety Notes; p 2/12)
ZA-0800 (-HS)
24 V DC, ±15 %
1,0 A (2.0 A)
800 N / 179.8 lbf
ZA-1500
1500 N
337.2 lbf
1000 N
224.8 lbf
1000 N
224.8 lbf
All forces + approx. 20 % switch-off reserve
800 N
179.8 lbf
(temporary)
Main closing edge
English
ZA-1000 (-HS)
ZA-1500 (-HS)
24 V DC, ±15 %
24 V DC, ±15 %
1,2 A (2.2 A)
1,4 A (2.5 A)
1000 N / 224.8 lbf
1500 N / 337.2 lbf
Higher forces can occur
on besides closing edges.
Danger of violent pressure
in handaccessible area.
3/12
ZA-1-PLP