Xylem sensus PolluStat User Manual page 15

Hide thumbs Also See for sensus PolluStat:
Table of Contents

Advertisement

DIB
Field
0
Message format
1
Heat energy E1 /
Cooling Energy
E3
2
Volume
3
Meter ID
4
Error flags
5
Meter date/time
6
Accumulated
energy at 24:00
6.6.2.6 Scheduled - Extended
The data message of Scheduled mode-Extended contains all the data fields from message format Standard with an
Size
Data type
1 byte
-
6-7 bytes
INT32
6 bytes
INT32
6 bytes
According to M- Bus
EN13757-3
identification field
4 bytes
INT8
6 bytes
INT32
6-7 bytes
INT32
Description
0x27 (= Scheduled – daily redundant)
Energy consumption (Wh, J, Cal, MBTU)
0406xxxxxxxx = MWh, 3 decimals = kWh
040Exxxxxxxx = GJ, 3 decimals
04FB0Dxxxxxxxx = Gcal, 3 decimals
04863Dxxxxxxxx = MMBTU, 3 decimals
Volume (m
)
3
0414xxxxxxxx = m
, 2 decimals
3
Meter ID
0C78xxxxxxxx
Error and warning flags
01FD17xx
Meter date and time (YY-MM-DD HH:MM)
046Dxxxxxxxx
Bit 31-28 = Year-high* Bit 27-24 = Month
Bit 23-21 = Year-low* Bit 20-16 = Day
Bit 15 = Summer time flag** Bit 14-13 = Century
Bit 12-8 = Hour
Bit 7 = Error flag
Bit 6 = Reserved for future use***
Bit 5-0 = Minute
*The year is read by combining the year-high
and year- low field. For example, year-high =
0010 and year-low
= 010 => year = 0010010
**0 = standard time, 1= daylight-saving time
***0 = timestamp is valid, 1 = timestamp is not
valid
Energy consumption (Wh, J)
4406xxxxxxxx = MWh, 3 decimals = kWh
440Exxxxxxxx = GJ, 3 decimals
44FB0Dxxxxxxxx = Gcal, 3 decimals
44863Dxxxxxxxx = MMBTU, 3 decimals
Note: Before a midnight reading has been
performed the Function field of the DIF is set
to "value during error state" to indicate that the
value is not valid.
Example:
740600000000 = MWh, 3 decimals = 0 kWh
Table 14: Message format Scheduled – daily redundant
15