5700-E Neutralizer Installation & Startup Guide
The advanced menus should have already been programmed for you, but it is a good idea to
verify the programming before you put the filter into service.
To enter the advanced menus, press both the Gear and Regen button at the same time. All
mode types will be flashing.
Advanced Menus
Set Regeneration Mode – This should be set to T for Time Mode, which displays the days and
hours left until the unit regenerates.
Set Time – Verify the correct time of day is set.
P1 Backwash – This should be set to 10 minutes for a Neutralizer Filter.
P2 Brine Draw – Set to 0 for a Neutralizer Filter.
P3 Rapid Rinse - This should be set to 6 minutes for a Neutralizer Filter.
BF Brine Refill - Set to 0 for a Neutralizer Filter.
Capacity – Verify that the capacity is set correctly according to this formula:
*Gallons = (Capacity/Hardness) x .75
For a 1.0 cf unit, set at 32.
For a 1.5 cf unit, set at 48.
You are done programming your valve! Now, put it into a backwash to check for leaks, drain the
media of fines, and get the filter ready to be put into service.