Huawei NetCol5000-A035 Quick Manual page 22

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

Amount of refrigerant to be charged for the NetCol5000-A025
Refrigerant
Actual length of
Charge Amount
the one-way
pipe(L)
Standard charge
0 m < L ≤ 10 m
amount (kg)
Refrigerant
10 m < L ≤ 100
charge (kg) =
m
Standard charge
+ Additional
charge
Scenarios without a low temperature component
On the left is the low pressure gauge. On the right is the high
pressure gauge.
The specification of needle valves is 7/16-20UNF.
Discharge
pipe needle
valve
NetCol500-
NetCol500-
A040
A040 including
a low
temperature
component
8.6
32.7
8.6 + (L - 10) x
32.7 + (L - 10)
0.17
x 0.19
Low-pressure
needle valve
Valve Valve
Nut
22
NetCol500-
A060/A120
9.4
9.4 + (L - 10) x
0.18
1. Leak checking
2. Vacuuming
3. Precharging refrigerant
Reducing
valve
Electronic
scale
NetCol500-
A060/A120
including a low
temperature
component
34
34 + (L - 10) x
0.18
Vacuum
pump
Refrigerant
cylinder

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol5000-a025

Table of Contents