Unigas RG75 Manual Of Installation - Use - Maintenance page 13

Light oil burners
Table of Contents

Advertisement

Fitting the burner to the boiler
To install the burner into the boiler, proceed as follows:
1
make a hole on the closing door of the combustion chamber as described on paragraph "Overall dimensions")
2
place the burner to the boiler: lift it up and handle it according to the procedure described on paragraph "Handling the burner";
3
place the 4 stud bolts (5), according to the burner's drilling plate described on paragraph "Overall dimensions";
4
fasten the 4 stud bolts;
5
place the ceramic fibre plait on the burner flange;
6
install the burner into the boiler;
7
fix the burner to the stud bolts, by means of the fixing nuts, according to the next picture.
8
After fitting the burner to the boiler, ensure that the gap between the blast tube and the refractory lining is sealed with appropriate
insulating material (ceramic fibre cord or refractory cement).
The burner is designed to work positioned according to the picture below. For different installations, please contact the Technical
Department.
Note: the figure is indicative only.
Keys
1
Burner
2
Fixing nut
3
Washer
4
Ceramic fibre plait
5
Stud bolt
7
Blast tube
SIDE UP
SIDE DOWN
13
PART II: INSTALLATION