Hydrostatic Test; Insulation; Maximum External Static Pressures - Carrier AirStream 42BHE06 Installation, Start-Up And Service Instructions Manual

System fan coil air conditioners
Hide thumbs Also See for AirStream 42BHE06:
Table of Contents

Advertisement

HYDROSTATIC TEST

When all joints are completed, perform hydrostatic test for leaks.
Hydronic systems should be tested with water (some components
are not designed to hold gas). If gas testing is necessary, pressure
must NOT exceed 80 psig. All chilled water piping and valves not
located over drain pans or drip lips must be insulated to prevent
damage from sweating. Vent all coils during final preparations.
(See Step 10, section 6 on page 18.)
WARNING
Never pressurize unit beyond the specified test pressure.
Always pressure test with an inert gas or fluid (nitrogen or
clear water) to avoid possible unit damage or personal injury in
the event of a leak during testing.
Check interior unit piping for signs of leakage from shipping dam-
age or mishandling. If leaks are found, notify your local Carrier
representative before initiating any repairs.
CAUTION
All water coils must be protected from freezing after initial
filling with water. Even if system is drained, unit coils may
still hold enough water to cause damage when exposed to
temperatures below freezing.
UNIT SIZE 42BHE, BVE
NOMINAL CFM
FILTERS (2-in. [50.8 mm] pleated)
Qty
Number...Size in. (mm)
Face Area (sq ft)
HYDRONIC COILS
Size in. (mm)
Face Area sq ft (sq m)
Fins per inch
Coil Water Volume approx. gal. 
per row of coil (liters)
FANS
Qty...Size (in.)
DX COIL CONN. LIQUID LINE (in.)
DX COIL CONN. SUCTION LINE
LEGEND
DX— Direct Expansion
Table 5 — Unit Physical Data
06
08
600
800
1000
1
1
16-1/2 x 24
16-1/2 x 24
18-1/4 x 33
(419 x 610)
(419 x 610)
(464 x 838)
2.8 (0.26)
2.8 (0.26)
4.2 (0.39)
15 x 20
15 x 20
15 x 29
(381 x 508)
(381 x 508)
(381 x 736)
2.1 (0.195) 2.1 (0.195)
3.0 (0.279)
10
10
0.240
0.240
0.324
(0.908)
(0.908)
(1.226)
1...9 x 4
1...9 x 6
1...10 x 4
(229 x 109)
(229 x 152)
(254 x 102)
1/4 nominal, 0.375 OD
3/4 in. (19.05 mm) nominal, 0.875 OD

INSULATION

Following the hydrostatic test, insulate all piping to unit to prevent
sweating.

MAXIMUM EXTERNAL STATIC PRESSURES

See Table 4 for maximum external static pressure information
when units are running at minimum airflow.
Table 4 — Maximum External Static Pressures at
42BHE/BVE
06
08
10
12
16
20
30
40
10
12
16
1200
1600
1
1
2
18-1/4 x 33
18-1/4 x 21-1/2
(464 x 838)
(464 x 546)
4.2 (0.39)
5.5 (0.51)
15 x 29
15 x 39
(381 x 736)
(381 x 991)
3.0 (0.279)
4.1 (0.381)
10
10
10
0.324
0.420
(1.226
(1.590)
1...10 x 7
1...11 x 10
(254 x 178)
(279 x 254)
1 nominal, 1.125 OD
14
Minimum Airflow
MAXIMUM ESP
MINIMUM CFM
300
400
700
900
1000
1800
2200
3200
20
30
2000
3000
2
2
20-1/2 x 22
29 x 22 (737
(521 x 559)
x 559)
6.3 (0.59)
8.9 (0.83)
18 x 40
27 x 40
(457 x 1016)
(686 x 1016)
4.9 (0.455)
7.7 (0.715)
10
10
0.492
0.768
(1.862)
(2.907)
1...12 x 9
1...12 x 12
(305 x 229)
(305 x 305)
1/2 nominal, 0.625 OD
1-1/2 nominal,
1.625 OD
(in. wg)
0.17
1.35
1.75
0.87
1.73
1.19
1.36
1.73
40
4000
2
29 x 29 (737
x 737)
11.7 (1.09)
27 x 54
(686 x 1372)
10.3 (0.957)
10
1.020
(3.861)
1...15 x 12
(381 x 305)