Gardner Denver EAQ99S Operating And Service Manual page 56

Electra-saver stationary base-mounted compressor
Table of Contents

Advertisement

To check the element, heat in oil -- it should be fully extended at 66° C. If the unit shuts down due to
high air discharge temperature, it may be that one or both thermostatic mixing valve elements (
page 44) are stuck open. Remove the mixing valve and clean all parts thoroughly when flushing the oil
system.
Air/oil under pressure will cause severe personal injury or death. Shut down
compressor, relieve system of all pressure, disconnect, lockout and tagout
power supply to the starter before removing valves, caps, plugs, fittings, bolts
and filters.
Compressor, air/oil reservoir, separation chamber and all piping and tubing
may be at high temperature during and after operation.
It is mandatory that any water cooled unit be installed in a shelter heated to
temperatures above freezing (0° C).
COMPRESSOR OIL COOLER - WATER-COOLED HEAT EXCHANGER (
exchanger oil cooler is a multiple pass type, with water in the tubes and oil in the shell. The oil
temperature is controlled by the thermal (thermostatic mixing) valve. The optional water control valve
may be used to conserve water.
Oil cooler malfunction may be traced by checking pressure at oil inlet and outlet. At normal operating air
service pressure (4.5 bar to 10.3 bar with the unit warm, a pressure drop of .2 to 1 bar can be expected
between the oil inlet and the oil outlet.
Water pressure drop from water inlet to outlet will vary with the inlet pressure and amount of water
flowing. A normal pressure drop may range from .3 bar to .7 bar. Any change in the pressure drop from
that normally held may indicate tube leakage or fouling and should be investigated.
In many instances, the cooling water supply for the heat exchanger will contain impurities in solution
and/or suspension. These substances can cause scale formation, corrosion and plugging of any water-
cooled heat exchanger equipment. Disregarding the possibility that one or more of these conditions exist
may result in increased maintenance and operation expense, reduced equipment life and emergency
shutdown. It is strongly recommended that a reputable, local water treatment concern be engaged to
establish the corrosion, scale forming and fouling tendency of the cooling water and take steps necessary
to remedy the situation if a problem does exist. The need for water treatment may involve only filtration
(screening) to remove debris, sand and/or salt in the cooling water supply. However, chemical treatment
methods may be necessary in certain instances to inhibit corrosion and/or remove dissolved solids, to
alter the water's tendency to form scale deposits, or prevent the growth of microorganisms. The normal
maintenance program for the unit should also include periodic cleaning of the tubes (water side) of the
heat exchanger to remove deposits which enhance fouling and corrosion.
13-10-616
Page 55
Figure 5-2
, page
44)
- The heat
Figure 5-2
,

Advertisement

Table of Contents
loading

Table of Contents