F.1 ES2 and EX2 Series - General Specifications
This specification is applicable to DVP-ES2/EX2 PLC CPU and their compatible extension
modules.
Item
Operating temperature
Storage temperature
Operating humidity
Storage humidity
Work environment
Installation location
Pollution degree
Ingress protection
(IP ratings)
Surge voltage withstand
level
Insulation voltage
Noise Immunity
Ground
Vibration / Shock
resistance
Ambient air
temperature-barometric
pressure-altitude
UL 94 Flame
Classifications
F - 2
0 to 55°C
-25 to 70°C
5–95%
No condensation
5–95%
No condensation
No corrosive gas exists.
In a control box
2
IP20
1,500 VAC (Primary-secondary), 1,500 VAC (Primary-PE),
500 VAC (Secondary-PE)
Above 5MΩ
The voltage between all inputs/outputs and the ground is 500 VDC.
ESD: IEC 61000-4-2 8KV Air Discharge, 4KV Contact Discharge
EFT: IEC 61000-4-4 Power Line: 2KV, Digital I/O: 1KV, Analog &
Communication I/O: 1KV
RS: IEC 61000-4-3 80MHz ~ 1GHz, 10V/m
Surge(IEC 61131-2, IEC 61000-4-5) :
AC power: CM ±2 kV, DM ±1 kV
DC power: CM ±0.5 kV, DM ±0.5 kV
Analog I/O, RS-232(shielded): CM ±1 kV
Digital I/O, RS-485 (unshielded): CM ±1 kV
The diameter of the ground should not be less than the diameters of
the cables connected to the terminals L and N.
It is required to use grounding if more than one PLC is being used
at the same time.
Vibration: IEC 60068-2-6(test Fc), 1g DIN rail mount
Shock resistance: IEC 60068-2-27(test Ea), 15 g, 11 ms pulse, 6
shocks in each of 3 axes
Operating: 1013 ~ 795hPa (0 ~ 2000 m)
Storage:1013 ~ 700hPa (0 ~ 3000m)
UL 94 V-0
Specifications