MAC3 HydroController HCW-MM User Manual page 45

Hide thumbs Also See for HydroController HCW-MM:
Table of Contents

Advertisement

49 MaxCorr.Motore
50 Configur. Relays
51 Inc Pres Booster
52 Autoc Tempo Vita
53 Autoc Tempo Vita
54 Corr.di picco
55 Abilita Remoto
Valore di intervento della protezione
amperometrica del dispositivo.
Determina la funzionalita' del relè. Il
relè d'allarme interviene per allarmi di
tipo elettrico ed idraulico.
Vers.HC STD (MM,MT,TT 5.5hp):
R1: Alarm (relè d'allarme)
R1: Run (relè di marcia)
R1: Remote Alarm (relè d'allarme su
contro remoto)
R1: Booster (relè comando pompa
booster)
Vers.HC ADV (MM,MT,TT 5.5hp):
R1:Alm R2:Run (relè allarme, relè
marcia)
R1:Alm R2:RemAlm (relè allarme, relè
allarme su controllo remoto)
R1:A R2:R R3:RA (relè allarme, relè
Marcia, relè Allarme su contr.Remoto)
R1:A R2:R R3:B1 (relè allarme, relè di
marcia, relè booster1)
R1:A R2:B1 R3:B2 (relè Allarme, relè
booster1, relè booster2)
R1:R R2:B1 R3:B2 (relè di marcia, relè
booster1, relè booster2)
R1,R2,R3:Booster (relè booster1,2,3)
Vers.HC TT (7.5Hp÷15hp):
R1:Alm R2:Alm (Relè allarme)
R1:Run R2:Run (Relè Marcia)
R1:Alm R2:Run (Relè allarme,relè
Marcia)
R1:Alm R2:B1 (Relè allarme,relè
booster1)
R1:Run R2:B1 (Relè Marcia,Relè
booster1)
R1:B1 R2:B2 (Relè Boster 1÷2)
R1:Alm R2:RemAlm (Relè allarme, relè
allarme su controllo remoto)
R1:Run R2:RemAlm (Relè marcia,relè
allarme su controllo remoto)
R1:B1 R2:RemAlm (Relè Booster, relè
allarme su controllo remoto)
Incremento della pressione impianto
quando il booster è attivo (default
+0.2bar)
Tempo di utilizzo della autoclave(min,
sec)
Tempo di utilizzo della autoclave(gg, h) Autoc Life Time
Imposta la corrente massima di picco,
superata la quale interviene la
protezione: "Corr.Picco Alta". E'
possibile visualizzare per 5 secondi la
corrente di spunto dalla schermata
principale tenendo premuto il tasto

all'avvio della pompa.
Se ON il drive è in standby e aspetta un
comando esterno per partire (es.
galleggiante di minima).
Max motor current Threshold of the amperometric
protection.
Relays Configur.
Determines the function to be
assigned to Relay. The alarm relay
means for both electric and hydraulic
alarms.
Vers.HC STD (MM,MT,TT 5.5hp):
R1: Alarm (Alarm relay)
R1: Run (Run relay)
R1: Remote Alarm (alarm relay on
R1: Booster (booster pump command
relay)
Vers.HC ADV (MM,MT,TT 5.5hp):
R1:Alm R2:Run (Alarm relay , run
relay)
R1:Alm R2:RemAlm (Alarm relay,
R1:A R2:R R3:RA (Alarm, Run,
booster pump command relay, alarm
relay on remote control)
R1:A R2:R R3:B1 (Alarm, Run,
booster pump command relay)
R1:A R2:B1 R3:B2 (Alarm, booster1,
booster2 pump command relay)
R1:R R2:B1 R3:B2 (Run,booster1,
booster2 pump command relay)
R1,R2,R3:Booster (booster1,2,3
pump command relay)
Vers.HC TT (7.5Hp÷15hp):
R1:Alm R2:Alm (Alarm relay)
R1:Run R2:Run (run relay)
R1:Alm R2:Run (Alarm relay, run
relay)
R1:Alm R2:B1 (Alarm relay,booster1)
R1:Run R2:B1 (run relay,booster1)
R1:B1 R2:B2 (Booster 1÷2)
R1:Alm R2:RemAlm (Alarm relay,
alarm relay on remote control)
R1:Run R2:RemAlm (run relay, alarm
relay on remote control)
R1:B1 R2:RemAlm (Booster, alarm
relay on remote control)
Inc Pres Booster
Increase the system pressure when
the booster is on (default +0.2 bar)
Autoc Life Time
Autoclave usage time (min, sec)
Autoclave usage time (day, hour)
Peak Current
Sets the maximum peak current
threshold for the "High peak curr"
alarm.
The current can be displayed for 5
seconds from the main menu
pressing
starts.
Remote enable
If ON, the inverter is in STANDBY
and wait external command to start
(eg. float switch)
remote control)
alarm relay on remote control)
key when the pump
45