SECTION 8 MAINTENANCE

8.10 Recommended Periodic Testing

Periodic testing of all boiler controls and safety devices is required to ensure they operate as designed. Take
precautions while tests are being performed to protect against bodily injury and property damage. The
owner or user of an automatic boiler system should set up a formal system of preventive maintenance and
testing. Tests should be conducted on a regular basis and the results recorded in a logbook.
TABLE 8-3: Recommended Periodic Testing
ITEM
FREQUENCY
NOTE: Refer to indicated sections of this manual for detailed procedures.
Gauges, monitors and
indicators
Instrument and
equipment settings
Semi-Annually Service Tech Verify factory settings
Firing Rate Control
Flue, vent, stack and
intake air duct
Spark Igniter-Injector
Air/Fuel Valve position
SSOV Leakage test
Flame failure
Flame signal strength
Low water level cut off
and alarm
Slow drain test
Semi-Annually
High water temp.
safety control test
Operating controls
Low air flow
High and low gas
pressure interlocks
Air/Fuel Valve purge
position switch
Air/Fuel Valve ignition
position switch
Safety valves
As required
Inspect burner
Semi-Annually Service Tech
components
Condensate Trap
Oxygen (O
) Level
2
ACTION BY
Daily
Operator
Visual inspection and record readings in operator log
Daily
Operator
Visual check against factory recommended specifications
Weekly
Operator
Verify factory settings
Check with combustion calibration test equipment (see
Section 4.2: Tools & Instruments for Combustion
Annually
Service Tech
Calibration in this guide), and the O
8.4: O
Monthly
Operator
Visually inspection condition and check for obstructions
Weekly
Operator
See Section 8.2: Ignitor-Injector of this guide.
Check position indicator dial. See Section 3.2: Start
Weekly
Operator
Sequence in this guide.
Check for leakage in accordance with the SSOV
Annually
Service Tech
manufacturer's (Siemens) recommendations.
Close manual gas shutoff valve and check safety
Weekly
Operator
shutdown. See Section 5.7: Flame Fault Test of this guide.
Weekly
Operator
Check flame strength in Controller's Unit Status screen.
Weekly
Operator
See Section 5.4: Low Water Level Fault Test in this Guide.
Perform slow drain test per ASME Boiler and Pressure
Operator
Vessel Code, Section IV.
Annually
Service Tech See Section 5.5: Water Temperature Fault Test.
Annually
Operator
See Section 2: Edge Controller Operation in this guide.
See Section 5.8: Air Flow Fault Tests and Section 8.8: Air
Monthly
Operator
Filter Cleaning and Replacement in this guide.
See Sections 5.2: Low Gas Pressure Test and 5.3: High Gas
Monthly
Operator
Pressure Test in this guide.
Annually
Service Tech See Section 5.10 Purge Switch Open During Purge.
Annually
Service Tech See Section 5.11: Ignition Switch Open During Ignition.
Operator
Check per A.S.M.E. Boiler Vessel Code, Section IV.
See Section 8.6: Burner Inspection in this guide.
Semi-
Operator
See Section 8.7: Condensate Drain Trap in this guide.
Annually
Monthly
Operator
Verify oxygen level is 3% - 8% during boiler operation.
REMARKS
Sensor in this guide).
2
sensor (see Section
2