Table 2: Error messages / flash codes red diagnostic LED
Flash codes (red)
1 flash pulse
2 flash pulses
3 flash pulses
4 flash pulses
5 flash pulses
6 flash pulses
7 flash pulses
8 flash pulses
9 flash pulses
Continuous red
7 调试与维护

7.1 Functional testing

The safety function of the safety components must be tested. The following conditions must be previously checked and
met:
1. Check max. axial misalignment of actuator and solenoid interlock.
2. Check max. angle displacement.
3. Make sure that it is not possible to lift the actuator in the Z axis above the extended bolt.
Flashes
Off
Designation
Error (warning) at output Y1
Error (warning) at output Y2
Error (warning) cross-wire short
Error (warning) temperature too
high
Actuator fault
Error control inputs /
electronic manual release
Fault with the actuator
detection  
Fault Block drive
Fault over/under voltage
Internal error
Off
0 V
Autonomous
switch-off after
30 min
30 min
30 min
30 min
0 min
-
0 min
0 min
0 min
0 min
26-27
24 V
0 V
Error cause
Fault in output test or voltage
at output Y1, although the
output is disabled.
Fault in output test or voltage
at output Y2, although the
output is disabled.
Cross-wire short between the
output cables or fault at both
outputs
The temperature measurement
reveals an internal temperature
that is too high
Incorrect or defective actuator
Invalid input condition of the
control inputs and/or of the
electronic manual release
Distance between the AZM400 and
the actuator is too large;
external magnetic fields prevent
detection
Actuator not properly aligned
for the solenoid interlock
Supply voltage outside
specification
Device defective
24 V