4. Testing the boiler

4.1

Preliminary checks

Before testing the boiler, it is recommended to check the following:
• the flue gas venting duct and the relevant terminal are installed in conformity with the instructions: with the boiler operating, there must
be no leakage of combustion by-products from any of the gaskets;
• the supply power to the boiler must be 230 V ~ 50 Hz;
• the system is correctly filled with water (pressure gauge reading 1 to 1.3 bar);
• any shut-off cocks in the system pipes are open;
• the mains gas type is correct for the boiler calibration: convert the boiler to the available gas when necessary; this operation must only be
performed by qualified technical personnel;
• the gas supply cock is open;
• there are no fuel gas leaks;
• the main switch installed ahead of the boiler is turned on;
• the 3-bar safety valve is not stuck;
• there are no water leaks;
• the pump has not seized.
WARNING
Should the boiler not be installed in compliance with the prevailing laws and standards, notify the system supervisor and do not
test the boiler.