Conditions
Possible cause
Emergency
RPO is active
power off
Fan fault
Fan abnormal
Site fault
Phase and neutral
conductor at input of
UPS system are
reversed
Over
Over temperature is too
temperature
high, UPS goes to
fault
bypass or stopped.
Output short
Output short circuit
circuit
occurred.
Action
1.Check the RPO connector
status
2.Reset the RPO fault through
LCD. Main menu – Control -
Reset fault state.
Check if the fan is running
normally
Site Fault detection disabled by
default. It can still be enabled /
disabled from the LCD settings
menu.
Reconnect all input wires.
Check the ventilation of the UPS
and check the ambient
temperature.
Check the output of UPS and
loads, make sure the short circuit
is removed before turning on
again.