Generac Power Systems MIH1.2 Owner's Manual page 25

Indirect fired heater
Table of Contents

Advertisement

Daily
50 Hour Break-In
Every 250 Hours
Every 500 Hours
Every 1,000 Hours
Every 2,000 Hours
Every 3,000 Hours
Every 6,000 Hours
As Required
1
During the initial operation of a new or rebuilt engine with Break-In Plus, replace the oil and filter after 50 hours on first run then every 250
hours.
2
Service intervals depend on sulfur content of the diesel fuel, oil pan capacity, and the oil and filter used.
NOTE: Refer to Riello operator manual for recommended burner maintenance.
Owner's Manual for Indirect Fired Heater
Table 4-1. Maintenance Schedule
Check engine oil level.
Check fuel level.
Check engine coolant level.
Drain water from fuel filters.
Inspect air cleaner, dust unloader valve, and indicator.
Perform visual walk around inspection.
Replace engine oil and engine oil filter.
Inspect and adjust cooling fan V-belt.
Replace engine oil and engine oil filter
Drain water from fuel tank.
Drain oil/water separator.
Service battery.
Inspect coolant pump.
Inspect open crankcase vent (OCV) system.
Remove and replace fuel filter elements.
Inspect belt wear.
Inspect belt tensioner.
Inspect cooling system.
Pressure test cooling system.
Check and adjust engine speeds.
Inspect engine mounts.
Inspect engine ground connection.
Inspect generator ball bearings.
Check the DC no load excitation voltage. See generator manual.
Inspect crankshaft vibration damper.
Adjust valve clearance.
Test glow plugs for continuity.
Flush and refill cooling system.
Test thermostat opening temperature.
Drain water from fuel filters.
Add coolant.
Replace air filter element.
Inspect primary air filter element.
Replace fan belt.
Inspect fuses.
Inspect electrical wiring and connections.
Purge fuel system.
1 2
Maintenance
21

Advertisement

Table of Contents
loading

Table of Contents