Advanced Configuration Using Display (Level Variables)

FAST FILLING OR EMPTYING

If the speed of liquid level rise or fall within the tank is greater than a rate of 1" per second (25.4mm/sec), set
Fast Level Change to YES.
Note: Fast filling or emptying can occur when multiple pumps are operating or when a weather event
increases the amount of liquid entering the tank.
1) From the Main Screen, press OK to advance
into the Main Menu.
2) Press OK to advance into the Configuration
Menu. Press Right Arrow to switch to
Advanced.
3) Press OK to advance into Advanced Menu.
4) Press Right Arrow (at least two times) to
scroll to Level Variables.
5) Press OK to advance into Level Variables
Menu (Low Dielectric will appear).
6) Press Right Arrow (at least two times) to
scroll to Fast Fill Rate.
7) Press OK to change the value for fast Fill
Rate.
a) Press Up Arrow to increase the value of
the number highlighted. Up Arrow will
scroll from 0 to 9 and back again.
b) Press Right Arrow to move one segment
to the right. Right Arrow will scroll left to
right and then back to the first segment.
c) When the value is correct, press OK to
save the setting.
8) When done, press ESC to return to the Range
Adjust Menu, press ESC to return to the
Advanced Menu, press ESC again to return to
the Configuration Menu and press ESC a
fourth time to return to the Main Screen.
|
30
Section Four
Normal Level Change
Fast Level Change
AD310320 Rev A