GENERAL
This device is a sounder for fire detection
panels that offer a strong sound and an
optical warning with a beacon that covers
many square metres. The main tone
frequency is 2.5kHz (±20%).
This device can co-operate with any fire
detection panel (BSR-2104, BSR-2114,
BS-1632, BS-1634, BS-1636, BS-636).

Installation and Connection

1. First, remove the retaining screw, place
a flat blade screwdriver in the holes of the
plastic hooks and remove the plastic cover
(Image 1 on page 2).
2. Use the supplied mounting parts to install
the siren's base on the wall. Place the
plastic plugs and fasten the screws to the
mounting holes.
3. Place the caps and make a hole in the
center using a small screwdriver. Pass
through the caps the cables to connect the
device.
4. The (+) of
connected to the (+) output of Alarm-1 or
Alarm-2 of the panel and the (-) of the
terminal block is connected to the (-) output
o f A l a r m - 1 o r A l a r m - 2 o f t h e
panel.Accordingly connect in parallel all the
sirens. (The maximum number of sirens
depends on the type of the panel).
5. On the last siren of the line, we must
Page 1 from 2
SOUNDER WITH BEACON FOR FIRE DETECTION PANEL

TECHNICAL CHARACTERISTICS

Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
the terminal block is
21-28V DC
40mA
4 red LEDs
88dB
Τype A
Wall
IP42
EN 54-3: 2014
0 to 60 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
141 x 141 x 95 mm
200gr.
2 years
connect in parallel with its power cables,
the terminal resistor that was removed
from the alarm contacts of the panel.
6. Refit the plastic cover until the plastic
hooks are securely attached (step 1) and
fasten the retaining screw (torque
0.6Nm).
7. Test the device after installation.
Certification
The electronic fire alarm sounder BS-
531 is certified from EVPU. Also
EVPU controls the production under
CPD number:
BS-531
Siren with beacon for
fire detection panel
1293-CPD-0356
EN-54-3
P C
. . 60
300 P.O. Box 06 Eginio Pierias Greece
o
921531000_09_013
1293
12

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BS-531 and is the answer not in the manual?

Questions and answers

Summary of Contents for olympia electronics BS-531

  • Page 1 TYPICAL WEIGHT 2 years GUARANTEE Thank you for your trust in our products. Olympia Electronics - European manufacturer. GENERAL connect in parallel with its power cables, This device is a sounder for fire detection the terminal resistor that was removed panels that offer a strong sound and an from the alarm contacts of the panel.
  • Page 2 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

Table of Contents