Download Print this page
olympia electronics ΒSR-5130/WP Quick Start Manual

olympia electronics ΒSR-5130/WP Quick Start Manual

Waterproof addressable sounder with integrated isolator

Advertisement

Quick Links

ΒSR-5130/WP
COMMUNICATION PROTOCOL
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
MAXIMUM SOUND LEVEL IN 1 METER
ENVIRONMENTAL TYPE
MOUNTING
MAXIMUM LOOP CURRENT (Ic max, -L in/out)
MAXIMUM SWITCH CURRENT (Is max, -L in/out)
MAXIMUM SERIES RESISTANCE (Zc max, -L in-out)
MAXIMUM LEAKAGE CURRENT IN ISOLATION MODE (I max, -L in/out)
ISOLATION VOLTAGE (Vso min-max)
RECONNECT VOLTAGE (Vsc min-max)
MOUNTING HEIGHT (x)
COVER AREA CODE
COVER AREA
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
This device is used as an audible warning sounder
in case of fire event. The sound level covers an
area of several square meters. It is compatible
with fire panels that support Olympia A Protocol.
CONNECTION AND MOUNTING
1. Unscrew the screw and remove the plastic
cover using a flat screwdriver to the point under
the screw (Picture 1 page 2).
2. Unscrew the four screws and detach the plastic
from the base (Picture 2).
3. Drill the holes needed to pass the connection
cables. Place the cable glands and open a hole to
the center with a small screwdriver. Pass the
connection cables through the glands of the device
(Picture 3).
4. Use the supplied mounting accessories to place
the base of the siren in height up to 2.4 meters from
the gound (Picture 3 page 2). Install the plastic
plugs and fasten the screws (with the supplied
rubber sealing ring and washer) in the mounting
holes. CAUTION!! Make sure that the base of the
siren is installed in the correct orientation.
Page 1 from 6
WATERPROOF ADDRESSABLE SOUNDER WITH INTEGRATED ISOLATOR
TECHNICAL CHARACTERISTICS
L
Thank you for your trust in our products
Olympia Electronics - European manufacturer
Olympia A Protocol
12-30V DC
90μΑ
7.4 to 35.9mΑ
101dB
Type Β
Wall mounted
300mΩ
25mA pulses (6ms duration every 2sec)
8.8 - 11
10.2 - 13
2.3 meters max
O-2,3-2,4-4,8
26.5m³ maximun
EN 54-3:2001, ΕΝ-54-17:2005
-25 to 70 C
Up to 95%
ABS/PC,PC
127x137x82 mm
313 gr.
2 years
5. To adjust the type of the sound indication use
the DIP switches 1 to 5, according to Table 1 (page 4).
6. To adjust the sound level use the DIP switches 6
to 7, according to Table 2 (page 6).
7. Refit the plastic and fasten the 4 screws you
removed in step 2.
8. Refit the plastic cover and fasten the screw.
9. Test the operation of the device through the panel
after the installation.
The BSR-5130/WP integrates an isolator short circuit
which activates automatically by disconnecting the
defective node from the loop and allowing it's
detection though the panel.
1A
5A
IP65
o
921513000_09_003
21
1293

Advertisement

loading
Need help?

Need help?

Do you have a question about the ΒSR-5130/WP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for olympia electronics ΒSR-5130/WP

  • Page 1 TYPICAL WEIGHT 2 years GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL 5. To adjust the type of the sound indication use This device is used as an audible warning sounder the DIP switches 1 to 5, according to Table 1 (page 4).
  • Page 2: Installation

    INSTALLATION Picture 2 Picture 1 Rubber WALL PLUG Sealing Ring Screw Washer Picture 3 UID: In every device there is a double sticker with the UID (Unique Identifier) number. This number is unique for each device. 921513000_09_003 Page 2 from 6...
  • Page 3 DIP switches for siren settings. Terminal connection to the loop. Loop OUT Loop IN 1 2 3 4 5 6 7 8 Loop IN +N1/+L -/-L +N2/+L +N1/+L -/-L +N2/+L Loop OUT Indicating LED. Flashes periodically in quiescent state. Lit steady in case of alarm. Turns off only after a reset.
  • Page 4 Table 1.1 Switch Frequency Main application setting Pattern Rate [1-2-3-4-5] Steady Continuous PFEER toxic gas 0-0-0-0-0 Intermitted 0.5Hz (1s On/1s Off) PFEER alert 1-0-0-0-0 Sweep 1s sweep German fire (DIN 33 404) 0-1-0-0-0 1200 - 500 Slow whoop 3s sweep, 0.5 sec silence Dutch fire (NEN 2575) 1-1-0-0-0 500 - 1200...
  • Page 5 Table 1.2 Sound level 1 Sound level 2 Sound level 3 Sound level 4 Alarm Alarm Alarm Alarm Switch dB (A) Consumption dB (A) Consumption dB (A) Consumption dB (A) Consumption setting [1-2-3-4-5] (mA) (mA) (mA) (mA) 0-0-0-0-0 11.2 11.2 24.3 27.4 1-0-0-0-0...
  • Page 6: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.